Tornare a: Cavi di sicurezza

JE-H(St)HRH...Bd FE180 E30-E90 fire alarm, black

halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30-E90* in accordance with DIN 4102-12

1 Conductor: solid
2 Insulation: cross-linked polymer, halogen-free
3 Drain wire: copper, Ø 0.8 mm
4 Inner covering: plastic tape, halogen-free
5 Shielding: Al-laminated plastic foil, halogen-free
6 Inner sheath: FRNC/LS0H
7 Armouring: galvanised steel wire band
8 Sheath: FRNC/LS0H

Descrizione

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor and outdoor applications. The steel wire braiding serves as mechanical protection. The fire alarm cables correspond to the demands of System Circuit Integrity E30-E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 110V.
Permitted operating temperature at conductor of +70°C.

  • Armatura (protezione per roditori) Galvanised steel wire braid
  • Conduttore Bare copper, solid, 0.8 mm diameter, VDE 0815
  • Colori delle anime DIN VDE 0815
  • Guaina interna Flame retardant polyolefin compound, VDE 0819 part 107, EN 50290-2-27 and VDE 0250-214 "HM2"
  • Isolamento Fire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-36
  • Shielding Al-laminated tape with copper drain wire Ø 0.8 mm
  • Zero alogeni nessun gas corrosivo IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
  • Propagazione della fiamma IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
  • Flame spread IEC 60332-3-22/-24 Cat. A/C, EN 60332-3-22/-24 Cat. A/C, VDE 0482-332-3-22/-24 Cat. A/C, AREI-RGIE Art.104-F2
  • Densità del fumo IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
  • Integrità del circuito di sistema DIN 4102-12, AREI-RGIE Art.104-FR2
  • Integrità del circuito (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), VDE 0482-362, AREI-RGIE Art.104-FR1
  • System Circuit Integrity dependent on installation method.
  • Capacitive coupling 0,8 mm, 100m @ 800Hz 200 pF/km
  • resistenza massima del loop 0,8 mm 73.2 Ω/km
  • Minimum insulation resistance 100 MΩ x km
  • operating capacity, 1km @ 800Hz 120 nF/km
  • peak voltage 225 V
  • Test voltage 50Hz, core/core 500 V
  • Test voltage 50Hz, core/screen 2000 V
  • Installation temperature -5 °C - +50 °C
  • Operating temperature -30 °C - +70 °C
  • Materiale della guaina esterna Flame retardant polyolefin compound VDE 0819 part 107, EN 50290-2-27 and VDE 0250-214 "HM 2"
  • Integrità del circuito E90
  • Integrità dell'isolamento FE 180
  • Resistenza minima allo schiacciamento / 10cm 1000 N
  • Curvatura minima durante l'installazione (multicore) 7.5 x D
  • Minimum bending radius permanent (multi core) 7.5 x D
  • Minimum number of impacts 10

Documentazione

EN DE NL FR CN ES IT
Certificato MPA file-icon Certificato MPA file-icon file-icon file-icon file-icon file-icon
Scheda tecnica Scheda tecnica Scheda tecnica Scheda tecnica Scheda tecnica file-icon Scheda tecnica Scheda tecnica

Versioni

Article No. Magazzino Prodotto Colore della guaina esternaNumero di coppieNumero di coreDiametro mmDiametro esterno della guaina [mm]Tasso di CU [kg/km]Weight [kg/km]Fire load [kWh/m]Unità di imballaggioGTIN / EAN
191071 JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 2x2x0,8 mm nero 2 2 0.8 mm9.3 25 125 0.26 kWh/mal metro 40393910069945
191554 JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 4x2x0,8 mm nero 4 2 0.8 mm12 45 194 0.39 kWh/mal metro 40393910069211
194070 JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 8x2x0,8 mm nero 8 2 0.8 mm18.2 85 419 0.93 kWh/mal metro 40393910064759
196354 JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 12x2x0,8 mm nero 12 2 0.8 mm19.1 mm126 490 1.01 kWh/mal metro 40393910061192
191070 JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 16x2x0,8 mm nero 16 2 0.8 mm20.5 166 557 1.17 kWh/mal metro 40393910069952
196265 JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 20x2x0,8 mm nero 20 2 0.8 mm22.3 206 680 1.32 kWh/mal metro 40393910061536
196347 JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 32x2x0,8 mm nero 32 2 0.8 mm26.7 mm326 912 1.72 kWh/mal metro 40393910061222