FE180 E30 CL
halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H
1 Conductor: solid / stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Inner Sheath: Polyolefin flame retardant, low smoke, zero halogen
6 Armouring: galvanised steel tape
7 Sheath: FRNC/LSZH






Descrizione
Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
- Outer sheath material Compound, HD 604 S1 part 5 H(16 mm2: in accordance with CENELEC HD 308 S2 and VDE 0293)
- Armatura (protezione per roditori) Single-core cable with copper tape (CLCU) and multicore cable with galvanised steel tape (CL)
- Conduttore Bare copper, solid or stranded, IEC 60228 and EN 60228 (≥16 mm2: VDE 0295)
- Colori delle anime CENELEC HD 308 S2
- Riempitrice HD 604 S1 part 5 H(≥16 mm2: halogen-free polyolefin compound)
- Guaina interna Compound, HD 604 S1 part 5 H(≥16 mm2: Polyolefin compound, VDE 0276-604, CENELEC HD 604 S1 ""HM 4"", flame-retardant)
- Isolamento Special compound, HD 604 S1 part 5 H(≥16 mm2: double-layer insulation, special compound, VDE 0266 "HXI1")
- Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA, SEV TPV11
- Flame Propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1, SEV TP 20B/3C 3.4.1.1
- Flame Spread IEC 60332-3-24 Cat. C, EN 60332-3-24 Cat. C, VDE 0482-332-3-24 Cat. C, AREI-RGIE Art.104-F2, SEV TP 20B/3C 3.4.1.3
- Smoke Density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD, SEV TP 20B/3C 3.4.3
- Integrità del circuito di sistema DIN 4102-12, AREI-RGIE Art.104-FR2
- Integrità del circuito (FE180) IEC 60331-11/-21 (180 minutes),VDE 0472-814 (FE180),BS 6387 C/W/Z,IEC 60331-1 (120 minutes),IEC 60331-2 (120 minutes),EN 50200 (PH120 minutes),VDE 0482-200 (PH120),VDE 0482-362,AREI-RGIE Art.104-FR1
- * System Circuit Integrity is dependent on installation method
- Tensione di prova a 50Hz 3500 V
- Installation temperature -5 °C - +50 °C
- Operating temperature -45 °C - +90 °C
- Curvatura minima durante l'installazione (anima singola) 15 x D
- Curvatura minima durante l'installazione (multicore) 12 x D
- Minimum bending radius permanent (multi core) 12 x D
- Minimum bending radius permanent (single core) 15 x D
Documentazione
Versioni
Article No. | Magazzino | Prodotto | Numero di core | Diametro mm² | Diametro esterno della guaina [mm] | Tasso di CU [kg\km] | Weight [kg\km] | Fire load [kWh\m] | Conductor |
---|---|---|---|---|---|---|---|---|---|
193886 | FE180 E30 CL | 3 | 1.5 | 11 | 43 kg/km | 211 | 0.46 kWh/m | solid | |
187199 | FE180 E30 CL | 3 | 2.5 | 12 | 72 kg/km | 255 | 0.50 kWh/m | solid | |
191097 | FE180 E30 CL | 3 | 4 | 14 | 115 kg/km | 373 | 0.69 kWh/m | solid | |
191121 | FE180 E30 CL | 3 | 6 | 15.8 | 173 kg/km | 487 | 0.90 kWh/m | solid | |
188354 | FE180 E30 CL | 3 | 10 | 18 | 288 kg/km | 655 | 1.20 kWh/m | solid | |
191595 | FE180 E30 CL | 4 | 2.5 | 14 | 96 kg/km | 296 | 0.56 kWh/m | solid | |
187167 | FE180 E30 CL | 4 | 4 | 16 | 154 kg/km | 408 | 0.79 kWh/m | solid | |
188352 | FE180 E30 CL | 4 | 6 | 17 | 230 kg/km | 539 | 1.06 kWh/m | solid | |
191038 | FE180 E30 CL | 5 | 2.5 | 14 | 120 kg/km | 388 | 0.76 kWh/m | solid | |
188350 | FE180 E30 CL | 5 | 4 | 16 | 192 kg/km | 488 | 1.05 kWh/m | solid | |
188353 | FE180 E30 CL | 5 | 6 | 17.5 | 288 kg/km | 643 | 1.28 kWh/m | solid | |
188397 | FE180 E30 CL | 5 | 10 | 21 | 480 kg/km | 971 | 1.76 kWh/m | solid | |
187197 | FE180 E30 CL | 7 | 2.5 | 16 | 168 kg/km | 476 | 0.91 kWh/m | solid | |
188355 | FE180 E30 CL | 7 | 6 | 19 | 403 kg/km | 801 | 1.53 kWh/m | solid | |
188356 | FE180 E30 CL | 7 | 10 | 23 | 672 kg/km | 1212 | 2.13 kWh/m | solid | |
192461 | FE180 E30 CL | 8 | 1.5 | 15 | 115 kg/km | 404 | 0.85 kWh/m | solid | |
187128 | FE180 E30 CL | 8 | 2.5 | 16 | 192 kg/km | 489 | 1.04 kWh/m | solid | |
191104 | FE180 E30 CL | 8 | 4 | 18 | 308 kg/km | 684 | 1.36 kWh/m | solid |