JE-H(St)H...Bd FE180 E30-E90 fire alarm

halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30-E90* in accordance with DIN 4102-12

1 Conductor: solid
2 Insulation: cross-linked polymer, zero halogen
3 Drain wire: Ø 0.8 mm
4 Separator: plastic tape, zero halogen
5 Shielding: Al-laminated tape, zero halogen
6 Sheath: FRNC/LSZH

Descrizione

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E30-E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 110V.
Permitted operating temperature at conductor of +70˚C.

  • Conduttore Bare copper, solid, 0.8 mm diameter, VDE 0815
  • Colori delle anime DIN VDE 0815
  • Isolamento Fire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-36
  • Shielding Al-laminated tape with copper drain wire Ø 0.8 mm
  • Zero alogeni nessun gas corrosivo IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
  • Propagazione della fiamma IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
  • Flame spread IEC 60332-3-22/-24 Cat. A/C, EN 60332-3-22/-24 Cat. A/C, VDE 0482-332-3-22/-24 Cat. A/C, AREI-RGIE Art.104-F2
  • Densità del fumo IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
  • Integrità del circuito di sistema DIN 4102-12, AREI-RGIE Art.104-FR2
  • Integrità del circuito (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), NBN 713-020 (Rf 1 1/2), VDE 0482-200 (PH120), VDE 0482-362, AREI-RGIE Art.104-FR1
  • System Circuit Integrity is dependent on installation method.
  • Capacitive coupling 0,8 mm, 100m @ 800Hz 200 pF/km
  • resistenza massima del loop 0,8 mm 73.2 Ω/km
  • Minimum insulation resistance 100 MΩ x km
  • operating capacity, 1km @ 800Hz 120 nF/km
  • peak voltage 225 V
  • Test voltage 50Hz, core/core 500 V
  • Test voltage 50Hz, core/screen 2000 V
  • Installation temperature -5 °C - +50 °C
  • Operating temperature -30 °C - +70 °C
  • Materiale della guaina esterna Flame retardant polyolefin compound VDE 0819 part 107, EN 50290-2-27 and VDE 0250-214 "HM 2"
  • Integrità del circuito E90
  • Integrità dell'isolamento FE 180
  • Resistenza minima allo schiacciamento / 10cm 1000 N
  • Curvatura minima durante l'installazione (multicore) 7.5 x D
  • Minimum bending radius permanent (multi core) 7.5 x D
  • Minimum number of impacts 10

Documentazione

EN DE NL FR CN ES IT
Certificato MPA file-icon Certificato MPA file-icon file-icon file-icon file-icon file-icon
Certificato VDE file-icon Certificato VDE file-icon file-icon file-icon file-icon file-icon
Scheda tecnica Scheda tecnica Scheda tecnica Scheda tecnica Scheda tecnica file-icon Scheda tecnica Scheda tecnica

Versioni

Article No. Magazzino Prodotto Colore della guaina esternaNumero di coppieNumero di coreDiametro mmDiametro esterno della guaina [mm]Tasso di CU [kg/km]Weight [kg/km]Fire load [kWh/m]Unità di imballaggioGTIN / EAN
188093 JE-H(St)H...Bd FE180 E30-E90 fire alarm 1x2x0,8 mm rosso 1 2 0.8 mm5.6 15 42 0.095 kWh/mal metro 40393910073164
188098 JE-H(St)H...Bd FE180 E30-E90 fire alarm 2x2x0,8 mm rosso 2 2 0.8 mm6.3 25 59 0.123 kWh/mal metro 40393910073126
188101 JE-H(St)H...Bd FE180 E30-E90 fire alarm 4x2x0,8 mm rosso 4 2 0.8 mm9 45 101 0.21 kWh/mal metro 40393910073102
188103 JE-H(St)H...Bd FE180 E30-E90 fire alarm 8x2x0,8 mm rosso 8 2 0.8 mm13.9 85 221 0.52 kWh/mal metro 40393910073089
188105 JE-H(St)H...Bd FE180 E30-E90 fire alarm 12x2x0,8 mm rosso 12 2 0.8 mm14.8 126 281 0.58 kWh/mal metro 40393910073065
188109 JE-H(St)H...Bd FE180 E30-E90 fire alarm 20x2x0,8 mm rosso 20 2 0.8 mm18.8 206 422 0.80 kWh/mal metro 40393910073027
188107 JE-H(St)H...Bd FE180 E30-E90 fire alarm 16x2x0,8 mm rosso 16 2 0.8 mm16.6 166 325 0.69 kWh/mal metro 40393910073041
188112 JE-H(St)H...Bd FE180 E30-E90 fire alarm 32x2x0,8 mm rosso 32 2 0.8 mm22 326 588 1.02 kWh/mal metro 40393910072990
188114 JE-H(St)H...Bd FE180 E30-E90 fire alarm 40x2x0,8 mm rosso 40 2 0.8 mm25.5 407 759 1.38 kWh/mal metro 40393910072976
188116 JE-H(St)H...Bd FE180 E30-E90 fire alarm 52x2x0,8 mm rosso 52 2 0.8 mm27.8 529 931 1.59 kWh/mal metro 40393910072952