(N)HXCH FE180 E90
halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E90 in accordance with DIN 4102-12
1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Concentric conductor: bare copper wire
6 Reinforcing helix: bare copper tape
7 Separator: plastic tape
8 Sheath: FRNC/LSZH






Descrizione
Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 400V.
Permitted operating temperature at conductor of +90˚C.
- Conduttore concentrico Bare copper wires with reinforced helix
- Colore della guaina esterna arancia
- Integrità del circuito (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
- Integrità del circuito di sistema DIN 4102-12, VdS 3423 (più di 16,0 mm²), AREI-RGIE Art.104-FR2
- Densità del fumo IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
- Zero alogeni nessun gas corrosivo IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
- Propagazione della fiamma AREI-RGIE Art.104-F1, EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2
- Flame spread IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Art.104-F2
- Tensione di prova a 50Hz 4000 V
- Installation temperature -5 °C - +50 °C
- Operating temperature -45 °C - +90 °C
- Integrità del circuito E90
- Integrità dell'isolamento FE 180
- Curvatura minima durante l'installazione (multicore) 12 x D
- Minimum bending radius permanent (multi core) 12 x D
Documentazione
Versioni
Article No. | Magazzino | Prodotto | CU rate (AT) | Numero di core | Diametro mm² | Diametro esterno della guaina [mm] | Weight [kg/km] | Fire load [kWh/m] | Conductor | Construction | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|---|
186071
|
(N)HXCH FE180 E90 3 x 1.5/1.5 | 73 | 3 | 1.5/1.5 | 13.2 | 245 | 0.65 kWh/m | solid | 3L | 40393910076813 | |
186195
|
(N)HXCH FE180 E90 3 x 2.5/2.5 | 113 | 3 | 2.5/2.5 | 14.1 | 303 | 0.72 kWh/m | solid | 3L | 40393910076257 | |
186197
|
(N)HXCH FE180 E90 3 x 4/4 | 168 | 3 | 4/4 | 15.6 | 400 | 0.84 kWh/m | solid | 3L | 40393910076233 | |
187278
|
(N)HXCH FE180 E90 3 x 6/6 | 250 | 3 | 6/6 | 16.9 | 521 | 0.94 kWh/m | solid | 3L | 40393910074048 | |
187279
|
(N)HXCH FE180 E90 3 x 10/10 | 408 | 3 | 10/10 | 18.6 | 727 | 1.15 kWh/m | solid | 3L | 40393910074031 | |
196386
|
(N)HXCH FE180 E90 3 x 16/16 | 670 | 3 | 16/16 | 24.4 | 1144 | 1.64 kWh/m | stranded | 3L | 40393910061109 | |
172417
|
(N)HXCH FE180 E90 3 x 35/16 | 1190 | 3 | 35/16 | 29 | 1944 | 2.25 kWh/m | stranded | 3L | 40393910078657 | |
187408
|
(N)HXCH FE180 E90 3 x 50/25 | 2083 | 3 | 50/25 | 32.5 | 2549 | 2.90 kWh/m | stranded | 3L | 40393910073782 | |
187409
|
(N)HXCH FE180 E90 3 x 70/35 | 2913 | 3 | 70/35 | 37.6 | 3536 | 3.42 kWh/m | stranded | 3L | 40393910073775 | |
187410
|
(N)HXCH FE180 E90 3 x 95/50 | 3949 | 3 | 95/50 | 41.9 | 4599 | 4.50 kWh/m | stranded | 3L | 40393910073768 | |
187411
|
(N)HXCH FE180 E90 3 x 120/70 | 4985 | 3 | 120/70 | 45.3 | 5688 | 5.02 kWh/m | stranded | 3L | 40393910073751 | |
187412
|
(N)HXCH FE180 E90 3 x 150/70 | 5100 | 3 | 150/70 | 50 | 6912 | 6.00 kWh/m | stranded | 3L | 40393910073744 | |
187414
|
(N)HXCH FE180 E90 3 x 240/120 | 8242 | 3 | 240/120 | 62.4 | 11153 | 9.08 kWh/m | stranded | 3L | 40393910073737 | |
186072
|
(N)HXCH FE180 E90 4 x 1.5/1.5 | 88 | 4 | 1.5/1.5 | 14.1 | 280 | 0.73 kWh/m | solid | 3LN | 40393910076806 | |
186196
|
(N)HXCH FE180 E90 4 x 2.5/2.5 | 138 | 4 | 2.5/2.5 | 15.1 | 350 | 0.82 kWh/m | solid | 3LN | 40393910076240 | |
186198
|
(N)HXCH FE180 E90 4 x 4/4 | 208 | 4 | 4/4 | 16.7 | 464 | 0.96 kWh/m | solid | 3LN | 40393910076226 | |
186199
|
(N)HXCH FE180 E90 4 x 6/6 | 309 | 4 | 6/6 | 18.1 | 615 | 1.13 kWh/m | solid | 3LN | 40393910076219 | |
186200
|
(N)HXCH FE180 E90 4 x 10/10 | 525 | 4 | 10/10 | 20.1 | 858 | 1.33 kWh/m | solid | 3LN | 40393910076202 | |
186131
|
(N)HXCH FE180 E90 4 x 16/16 | 829 | 4 | 16/16 | 25.3 | 1398 | 1.81 kWh/m | stranded | 3LN | 40393910076783 | |
186132
|
(N)HXCH FE180 E90 4 x 25/16 | 1190 | 4 | 25/16 | 28.9 | 1898 | 2.28 kWh/m | stranded | 3LN | 40393910076776 | |
186133
|
(N)HXCH FE180 E90 4 x 35/16 | 1590 | 4 | 35/16 | 31.6 | 2382 | 2.60 kWh/m | stranded | 3LN | 40393910076769 | |
186134
|
(N)HXCH FE180 E90 4 x 50/25 | 2295 | 4 | 50/25 | 36.7 | 3249 | 3.49 kWh/m | stranded | 3LN | 40393910076752 | |
186135
|
(N)HXCH FE180 E90 4 x 70/35 | 3210 | 4 | 70/35 | 41.3 | 4370 | 4.25 kWh/m | stranded | 3LN | 40393910076745 | |
186136
|
(N)HXCH FE180 E90 4 x 95/50 | 4383 | 4 | 95/50 | 46.4 | 5732 | 5.53 kWh/m | stranded | 3LN | 40393910076738 | |
186137
|
(N)HXCH FE180 E90 4 x 120/70 | 5613 | 4 | 120/70 | 50.1 | 7078 | 6.25 kWh/m | stranded | 3LN | 40393910076721 | |
186138
|
(N)HXCH FE180 E90 4 x 150/70 | 6813 | 4 | 150/70 | 55.3 | 8631 | 7.58 kWh/m | stranded | 3LN | 40393910076714 | |
186139
|
(N)HXCH FE180 E90 4 x 185/95 | 8499 | 4 | 185/95 | 60.8 | 10727 | 9.18 kWh/m | stranded | 3LN | 40393910076707 | |
186140
|
(N)HXCH FE180 E90 4 x 240/120 | 10985 | 4 | 240/120 | 69.2 | 13947 | 11.60 kWh/m | stranded | 3LN | 40393910076691 | |
186073
|
(N)HXCH FE180 E90 7 x 1.5/2.5 | 139 | 7 | 1.5/2.5 | 16.1 | 390 | 0.94 kWh/m | solid | 7L | 40393910076790 | |
191096
|
(N)HXCH FE180 E90 7 x 2.5/2.5 | 208 | 7 | 2.5/2.5 | 17.3 | 485 | 1.05 kWh/m | solid | 7L | 40393910069792 | |
187415
|
(N)HXCH FE180 E90 12 x 1.5/2.5 | 214 | 12 | 1.5/2.5 | 20.2 | 589 | 1.38 kWh/m | solid | 12L | 40393910073720 | |
187402
|
(N)HXCH FE180 E90 24 x 1.5/6 | 430 | 24 | 1.5/6 | 27 | 1066 | 2.32 kWh/m | solid | 24L | 40393910073812 | |
187403
|
(N)HXCH FE180 E90 24 x 2.5/10 | 696 | 24 | 2.5/10 | 29.6 | 1419 | 2.69 kWh/m | solid | 24L | 40393910073805 | |
187404
|
(N)HXCH FE180 E90 30 x 1.5/6 | 499 | 30 | 1.5/6 | 28.4 | 1232 | 2.67 kWh/m | solid | 30L | 40393910073799 |