FE180 flex
halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H
1 Conductor: stranded
2 Fire barrier: high-performance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Sheath: FRNC / LSZH






Descrizione
Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
- Materiale della guaina esterna Compound, HD 604 S1 part 5 H
- Conduttore Bare copper, stranded, IEC 60228 class 5, EN 60228
- Colori delle anime CENELEC HD 308 S2
- Riempitrice HD 604 S1 part 5 H
- Isolamento Special compound, HD 604 S1 part 5 H
- Zero alogeni nessun gas corrosivo IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA, SEV TPV11
- Propagazione della fiamma IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1, SEV TP 20B/3C 3.4.1.1
- Flame Spread IEC 60332-3-24 Cat. C, EN 60332-3-24 Cat. C, VDE 0482-332-3-24 Cat. C, AREI-RGIE Art.104-F2, SEV TP 20B/3C 3.4.1.3
- Densità del fumo IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD, SEV TP 20B/3C 3.4.3
- Integrità del circuito (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), VDE 0482-362, AREI-RGIE Art.104-FR1
- Additional dimensions available on request.
- Tensione di prova a 50Hz 2000 V
- Installation temperature -5 °C - +50 °C
- Operating temperature -45 °C - +90 °C
- Integrità dell'isolamento FE 180
- Curvatura minima durante l'installazione (multicore) 6 x D
- Minimum bending radius permanent (multi core) 4 x D
Documentazione
Versioni
Article No. | Magazzino | Prodotto | Numero di core | Diametro mm² | Diametro esterno della guaina [mm] | Tasso di CU [kg/km] | Weight [kg/km] | Fire load [kWh/m] | Construction | GTIN |
---|---|---|---|---|---|---|---|---|---|---|
188335
|
FE180 flex 3 x 1.5 | 3 | 1.5 | 8.5 | 43 | 123 | 0.27 kWh/m | LNPE | 40393910072419 | |
187554
|
FE180 flex 5 x 1.5 | 5 | 1.5 | 10.3 | 72 | 182 | 0.40 kWh/m | 3LNPE | 40393910073645 | |
187179
|
FE180 flex 5 x 2.5 | 5 | 2.5 | 12.1 | 120 | 271 | 0.55 kWh/m | 3LNPE | 40393910074505 | |
192367
|
FE180 flex 7 x 1.5 | 7 | 1.5 | 11 | 101 | 222 | 0.44 kWh/m | 6LPE | 40393910067620 | |
185228
|
FE180 flex 8 x 1.5 | 8 | 1.5 | 12.4 | 115 | 273 | 0.56 kWh/m | 6LNPE | 40393910077315 | |
191059
|
FE180 flex 12 x 1.5 | 12 | 1.5 | 14 | 173 | 313 | 0.72 kWh/m | 11LPE | 40393910070033 | |
191060
|
FE180 flex 16 x 1.5 | 16 | 1.5 | 16 | 231 | 410 | 0.89 kWh/m | 15LPE | 40393910070026 | |
191061
|
FE180 flex 21 x 1.5 | 21 | 1.5 | 18 | 303 | 527 | 1.10 kWh/m | 20LPE | 40393910070019 |