FE180 E30 CL
halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H
1 Conductor: solid / stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Inner Sheath: Polyolefin flame retardant, low smoke, zero halogen
6 Armouring: galvanised steel tape
7 Sheath: FRNC/LSZH






Description
Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
- Maintien de l'isolation (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
- Maintien de fonction DIN 4102-12, AREI-RGIE Art.104-FR2
- Densité De Fumée EN 61034-1/-2, IEC 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD, SEV TP 20B/3C 3.4.3
- Zéro halogène, pas de gaz corrosifs EN 60754-1/-2, IEC 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA, SEV TPV11
- Propagation de flamme IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1, SEV TP 20B/3C 3.4.1.1
- Propagation de la flamme EN 60332-3-24, IEC 60332-3-24, VDE 0482-332-3-24, AREI-RGIE Art.104-F2, SEV TP 20B/3C 3.4.1.3
- Température d'installation -5 °C - +50 °C
- Température de fonctionnement -45 °C - +90 °C
- Intégrité du circuit E30
- Intégrité de l'isolation FE 180
- Rayon de courbure minimal fixe (câble monoconducteur) 15 x D
- Rayon de courbure minimal fixe (câbles multiconducteurs) 12 x D
- Rayon de courbure minimal lors de l'installation (câble monoconducteur) 15 x D
- Rayon de courbure minimal lors de l'installation (câbles multiconducteurs) 12 x D
- Tension d'essai à 50 Hz 3500 V
- * System Circuit Integrity is dependent on installation method
Documentation
Versions
N° d'article | Stock | Produit | Nombres de coeurs | Diameter mm² | Diamètre de la gaine extérieure [mm] | Poids CU [kg/km] | Poids [kg/km] | Charge d'incendie[kWh/m] | Conducteur | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|
193886
|
FE180 E30 CL | 3 | 1.5 | 11 | 43 | 210 | 0.46 kWh/m | massif | 40393910065367 | |
187199
|
FE180 E30 CL | 3 | 2.5 | 12 | 72 | 255 | 0.50 kWh/m | massif | 40393910074345 | |
191097
|
FE180 E30 CL | 3 | 4 | 14 | 115 | 373 | 0.69 kWh/m | massif | 40393910069785 | |
191121
|
FE180 E30 CL | 3 | 6 | 15.8 | 173 | 481 | 0.90 kWh/m | massif | 40393910069648 | |
188354
|
FE180 E30 CL | 3 | 10 | 18 | 288 | 651 | 1.20 kWh/m | massif | 40393910072303 | |
191595
|
FE180 E30 CL | 4 | 2.5 | 14 | 96 | 296 | 0.56 kWh/m | massif | 40393910069143 | |
187167
|
FE180 E30 CL | 4 | 4 | 16 | 154 | 408 | 0.79 kWh/m | massif | 40393910074512 | |
188352
|
FE180 E30 CL | 4 | 6 | 17 | 230 | 535 | 1.06 kWh/m | massif | 40393910072327 | |
191038
|
FE180 E30 CL | 5 | 2.5 | 14 | 120 | 388 | 0.76 kWh/m | massif | 40393910070040 | |
188350
|
FE180 E30 CL | 5 | 4 | 16 | 192 | 488 | 1.05 kWh/m | massif | 40393910072341 | |
188353
|
FE180 E30 CL | 5 | 6 | 17.5 | 288 | 640 | 1.28 kWh/m | massif | 40393910072310 | |
188397
|
FE180 E30 CL | 5 | 10 | 21 | 480 | 964 | 1.76 kWh/m | massif | 40393910072082 | |
187197
|
FE180 E30 CL | 7 | 2.5 | 16 | 168 | 476 | 0.91 kWh/m | massif | 40393910074369 | |
188355
|
FE180 E30 CL | 7 | 6 | 19 | 403 | 794 | 1.53 kWh/m | massif | 40393910072297 | |
188356
|
FE180 E30 CL | 7 | 10 | 23 | 672 | 1201 | 2.13 kWh/m | massif | 40393910072280 | |
192461
|
FE180 E30 CL | 8 | 1.5 | 15 | 115 | 403 | 0.85 kWh/m | massif | 40393910067477 | |
187128
|
FE180 E30 CL | 8 | 2.5 | 16 | 192 | 489 | 1.04 kWh/m | massif | 40393910074642 | |
191104
|
FE180 E30 CL | 8 | 4 | 18 | 308 | 684 | 1.36 kWh/m | massif | 40393910069754 |