Retour à: Câbles de sécurité

FE180 E30

halogen-free, with improved fire characteristics,
in accordance to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H
30 minutes system circuit integrity* with reference to DIN 4102-12

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Sheath: FRNC/LSZH

Description

Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.

  • Zéro halogène, pas de gaz corrosifs IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA, SEV TPV11
  • Propagation de flamme IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1, SEV TP 20B/3C 3.4.1.1
  • Propagation de la flamme IEC 60332-3-24 Cat. C, EN 60332-3-24 Cat. C, VDE 0482-332-3-24 Cat. C, AREI-RGIE Art.104-F2, SEV TP 20B/3C 3.4.1.3
  • Densité De Fumée IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD, SEV TP 20B/3C 3.4.3
  • Maintien de l'isolation (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), VDE 0482-362, AREI-RGIE Art.104-FR1
  • Température d'installation -5 °C - +50 °C
  • Température de fonctionnement -45 °C - +90 °C
  • Intégrité du circuit E30
  • Intégrité de l'isolation FE 180
  • Rayon de courbure minimal fixe (câble monoconducteur) 15 x D
  • Rayon de courbure minimal fixe (câbles multiconducteurs) 12 x D
  • Rayon de courbure minimal lors de l'installation (câble monoconducteur) 15 x D
  • Rayon de courbure minimal lors de l'installation (câbles multiconducteurs) 12 x D
  • Remarques sur le rayon de courbure 50% reduction if installation at 30°C and with a template
  • Tension d'essai à 50 Hz 3500 V
  • System Circuit Integrity is depemndent on installation method.

Documentation

EN DE NL FR CN ES IT
Fiche technique Fiche technique Fiche technique Fiche technique Fiche technique file-icon Fiche technique Fiche technique

Versions

N° d'article Stock Produit Nombres de coeursDiameter mm²Diamètre de la gaine extérieure [mm]Poids CU [kg/km]Poids [kg/km]Charge d'incendie[kWh/m]ConducteurConstructionGTIN
191118 FE180 E30 2 x 1.5 2 1.5 7.8 29 102 0.22 kWh/mmassif LN 40393910069662
188360 FE180 E30 2 x 1,5 2 1.5 7.8 29 102 0.22 kWh/mmassif 2L 40393910072242
191119 FE180 E30 2 x 2.5 2 2.5 9 48 142 0.28 kWh/mmassif LN 40393910069655
190402 FE180 E30 2 x 2,5 2 2.5 9 48 142 0.28 kWh/mmassif 2L 40393910070996
187180 FE180 E30 3 x 1.5 3 1.5 8.3 43 121 0.25 kWh/mmassif LNPE 40393910074499
187184 FE180 E30 3 x 2.5 3 2.5 9.5 72 169 0.31 kWh/mmassif LNPE 40393910074451
187187 FE180 E30 3 x 4 3 4 11 115 243 0.41 kWh/mmassif LNPE 40393910074420
187189 FE180 E30 3 x 6 3 6 12.5 173 329 0.51 kWh/mmassif LNPE 40393910074406
187182 FE180 E30 4 x 1.5 4 1.5 9.1 58 147 0.29 kWh/mmassif 3LPE 40393910074475
190502 FE180 E30 4 x 2.5 4 2.5 10.5 96 209 0.38 kWh/mmassif 3LPE 40393910070828
192352 FE180 E30 4 x 4 4 4 12.2 154 304 0.49 kWh/mmassif 3LPE 40393910067705
192353 FE180 E30 4 x 6 4 6 13.8 230 409 0.61 kWh/mmassif 3LPE 40393910067699
187183 FE180 E30 5 x 1.5 5 1.5 9.9 72 177 0.35 kWh/mmassif 3LNPE 40393910074468
187186 FE180 E30 5 x 2.5 5 2.5 11.6 120 255 0.47 kWh/mmassif 3LNPE 40393910074437
187188 FE180 E30 5 x 4 5 4 13.4 192 371 0.61 kWh/mmassif 3LNPE 40393910074413
187190 FE180 E30 5 x 6 5 6 15.2 288 504 0.76 kWh/mmassif 3LNPE 40393910074390
186267 FE180 E30 7 x 1.5 7 1.5 10.8 100.8 220 0.41 kWh/mmassif 6LPE 40393910076172
186268 FE180 E30 7 x 2.5 7 2.5 12.5 168 319 0.53 kWh/mmassif 6LPE 40393910076165
187201 FE180 E30 7 x 6 7 6 16.7 403 644 0.89 kWh/mmassif 6LPE 40393910074338
187108 FE180 E30 8 x 1.5 8 1.5 11.9 115 258 0.48 kWh/mmassif 7LPE 40393910074680
188345 FE180 E30 10 x 1.5 10 1.5 13.8 144 319 0.69 kWh/mmassif 9LPE 40393910072372
186269 FE180 E30 12 x 1.5 12 1.5 14.2 172.8 364 0.66 kWh/mmassif 11LPE 40393910076158
192479 FE180 E30 12 x 2.5 12 2.5 16.7 288 536 0.88 kWh/mmassif 11LPE 40393910067354
187109 FE180 E30 21 x 1.5 21 1.5 17.7 303 578 0.99 kWh/mmassif 20LPE 40393910074673
190412 FE180 E30 27 x 1.5 27 1.5 20.4 389 752 1.30 kWh/mmassif 26LPE 40393910070972