(N)HXCH FE180 E30-E60 B2ca
halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E30-E60* in accordance with DIN 4102-12
Reacción al fuego según EN 13501-6
1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Concentric conductor: bare copper wire
6 Reinforcing helix: bare copper tape
7 Separator: plastic tape
8 Sheath: FRNC/LSZH






Descripción
Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E30-E60* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 400V.
Permitted operating temperature at conductor of +90˚C.
- For use in critical fire safety infrastructure (in compliance with VKF, ASTRA, Tunnels Directive, etc.), particularly in escape routes and emergency lines.
- Reacción al fuego (Euroclases) EN 13501-6: B2ca
- Cero halógeno gases no corrosivos IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
- Propagación de llamas IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
- Dispersión de llamas IEC 60332-3-22/-24 Cat. A/C, EN 60332-3-22/-24 Cat. A/C, VDE 0482-332-3-22/-24 Cat. A/C, AREI-RGIE Art.104-F2
- Densidad de humo IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
- Integridad del Sistema de Circuito DIN 4102-12, AREI-RGIE Art.104-FR2
- Integridad de circuito (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), VDE 0482-362, AREI-RGIE Art.104-FR1
- System Circuit Integrity is dependent on installation method.
- Tensión de prueba a 50 Hz 4000 V
- Temperatura de instalación -5 °C - +50 °C
- Temperatura de funcionamiento -45 °C - +90 °C
- Color de la funda exterior anaranjado
- Integridad de circuito E30-E60*
- Integridad del aislamiento FE 180
- Mínimo de flexión durante la instalación (multinúcleo) 12 x D
- Plegado mínimo durante la instalación (núcleo único) 15 x D
- Radio de flexión mínimo permanente (multinúcleo) 12 x D
- Radio de flexión mínimo permanente (núcleo único) 15 x D
- Screened No
Documentos
Versiones
N° de artículo | Inventario | Producto | Velocidad CU (AT) | Reacción al fuego | Color de la funda exterior | Número de núcleos | Diámetro [mm2] | Diámetro exterior de la vaina [mm] | Peso [kg/km] | Carga de fuego [kWh/m] | Conductor | Construcción | Unidad de embalaje | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
18694300BZ
|
(N)HXCH FE180 E30-E60 2 x 1.5/1.5 | 54 | B2ca-s1a,d1,a1 | anaranjado | 2 | 1.5/1.5 | 12.7 mm | 222 | 0.551 kWh/m | de corrido | LN | por metro | 40393910037883 | |
18694400BZ
|
(N)HXCH FE180 E30-E60 2 x 2.5/2.5 | 83 | B2ca-s1a,d1,a1 | anaranjado | 2 | 2.5/2.5 | 13.5 mm | 270 | 0.612 kWh/m | de corrido | LN | por metro | 40393910037876 | |
18723200BZ
|
(N)HXCH FE180 E30-E60 2 x 4/4 | 123 | B2ca-s1a,d1,a1 | anaranjado | 2 | 4/4 | 14.9 mm | 352 | 0.706 kWh/m | de corrido | LN | por metro | 40393910037296 | |
18723400BZ
|
(N)HXCH FE180 E30-E60 2 x 6/6 | 182 | B2ca-s1a,d1,a1 | anaranjado | 2 | 6/6 | 16 mm | 430 | 0.79 kWh/m | de corrido | LN | por metro | 40393910037289 | |
18694500BZ
|
(N)HXCH FE180 E30-E60 3 x 1.5/1.5 | 73 | B2ca-s1a,d1,a1 | anaranjado | 3 | 1.5/1.5 | 13.2 mm | 247 | 0.599 kWh/m | de corrido | 3L | por metro | 40393910037869 | |
18694600BZ
|
(N)HXCH FE180 E30-E60 3 x 2.5/2.5 | 113 | B2ca-s1a,d1,a1 | anaranjado | 3 | 2.5/2.5 | 14.1 mm | 305 | 0.784 kWh/m | de corrido | 3L | por metro | 40393910037852 | |
18723800BZ
|
(N)HXCH FE180 E30-E60 3 x 16/16 | 670 | B2ca-s1a,d1,a1 | anaranjado | 3 | 16/16 | 21.3 mm | 1029 | 1.348 kWh/m | trenzado | 3L | por metro | 40393910037272 | |
18723900BZ
|
(N)HXCH FE180 E30-E60 3 x 25/16 | 902 | B2ca-s1a,d1,a1 | anaranjado | 3 | 25/16 | 25 mm | 1435 | 1.799 kWh/m | trenzado | 3L | por metro | 40393910037265 | |
18724000BZ
|
(N)HXCH FE180 E30-E60 3 x 35/16 | 1190 | B2ca-s1a,d1,a1 | anaranjado | 3 | 35/16 | 37.3 mm | 1802 | 2.096 kWh/m | trenzado | 3L | por metro | 40393910037258 | |
18724100BZ
|
(N)HXCH FE180 E30-E60 3 x 50/25 | 1723 | B2ca-s1a,d1,a1 | anaranjado | 3 | 50/25 | 31.7 mm | 2454 | 2.689 kWh/m | trenzado | 3L | por metro | 40393910037241 | |
18724200BZ
|
(N)HXCH FE180 E30-E60 3 x 70/35 | 2410 | B2ca-s1a,d1,a1 | anaranjado | 3 | 70/35 | 36 mm | 3346 | 3.32 kWh/m | trenzado | 3L | por metro | 40393910037234 | |
18698500BZ
|
(N)HXCH FE180 E30-E60 3 x 95/50 | 3949 | B2ca-s1a,d1,a1 | anaranjado | 3 | 95/50 | 41.1 mm | 4451 | 4.416 kWh/m | trenzado | 3L | por metro | 40393910037524 | |
18698600BZ
|
(N)HXCH FE180 E30-E60 3 x 120/70 | 4985 | B2ca-s1a,d1,a1 | anaranjado | 3 | 120/70 | 44.5 mm | 5530 | 5.002 kWh/m | trenzado | 3L | por metro | 40393910037517 | |
18698700BZ
|
(N)HXCH FE180 E30-E60 3 x 150/70 | 5313 | B2ca-s1a,d1,a1 | anaranjado | 3 | 150/70 | 49.2 mm | 6737 | 6.114 kWh/m | trenzado | 3L | por metro | 40393910037500 | |
18698800BZ
|
(N)HXCH FE180 E30-E60 3 x 240/120 | 8585 | B2ca-s1a,d1,a1 | anaranjado | 3 | 240/120 | 61.5 mm | 10918 | 9.391 kWh/m | trenzado | 3L | por metro | 40393910037494 | |
18694700BZ
|
(N)HXCH FE180 E30-E60 4 x 1.5/1.5 | 88 | B2ca-s1a,d1,a1 | anaranjado | 4 | 1.5/1.5 | 14.1 mm | 282 | 0.677 kWh/m | de corrido | 3LN | por metro | 40393910037845 | |
18694800BZ
|
(N)HXCH FE180 E30-E60 4 x 2.5/2.5 | 138 | B2ca-s1a,d1,a1 | anaranjado | 4 | 2.5/2.5 | 15.1 mm | 351 | 0.754 kWh/m | de corrido | 3LN | por metro | 40393910037838 | |
18694900BZ
|
(N)HXCH FE180 E30-E60 4 x 4/4 | 208 | B2ca-s1a,d1,a1 | anaranjado | 4 | 4/4 | 16.7 mm | 466 | 0.87 kWh/m | de corrido | 3LN | por metro | 40393910037821 | |
18695000BZ
|
(N)HXCH FE180 E30-E60 4 x 6/6 | 309 | B2ca-s1a,d1,a1 | anaranjado | 4 | 6/6 | 18.1 mm | 614 | 1.051 kWh/m | de corrido | 3LN | por metro | 40393910037814 | |
18695100BZ
|
(N)HXCH FE180 E30-E60 4 x 10/10 | 525 | B2ca-s1a,d1,a1 | anaranjado | 4 | 10/10 | 20.1 mm | 860 | 1.25 kWh/m | de corrido | 3LN | por metro | 40393910037807 | |
18698900BZ
|
(N)HXCH FE180 E30-E60 4 x 16/16 | 829 | B2ca-s1a,d1,a1 | anaranjado | 4 | 16/16 | 23.4 mm | 1247 | 1.494 kWh/m | trenzado | 3LN | por metro | 40393910037487 | |
18699000BZ
|
(N)HXCH FE180 E30-E60 4 x 25/16 | 1190 | B2ca-s1a,d1,a1 | anaranjado | 4 | 25/16 | 27.2 mm | 1744 | 2.106 kWh/m | trenzado | 3LN | por metro | 40393910037470 | |
18699100BZ
|
(N)HXCH FE180 E30-E60 4 x 35/16 | 1590 | B2ca-s1a,d1,a1 | anaranjado | 4 | 35/16 | 29.8 mm | 2199 | 2.432 kWh/m | trenzado | 3LN | por metro | 40393910037463 | |
18699200BZ
|
(N)HXCH FE180 E30-E60 4 x 50/25 | 2295 | B2ca-s1a,d1,a1 | anaranjado | 4 | 50/25 | 34.8 mm | 3029 | 3.298 kWh/m | trenzado | 3LN | por metro | 40393910037456 | |
18699300BZ
|
(N)HXCH FE180 E30-E60 4 x 70/35 | 3210 | B2ca-s1a,d1,a1 | anaranjado | 4 | 70/35 | 39.5 mm | 4132 | 3.968 kWh/m | trenzado | 3LN | por metro | 40393910037449 | |
18699400BZ
|
(N)HXCH FE180 E30-E60 4 x 95/50 | 4383 | B2ca-s1a,d1,a1 | anaranjado | 4 | 95/50 | 45.2 mm | 5509 | 5.298 kWh/m | trenzado | 3LN | por metro | 40393910037432 | |
18699500BZ
|
(N)HXCH FE180 E30-E60 4 x 120/70 | 5613 | B2ca-s1a,d1,a1 | anaranjado | 4 | 120/70 | 49.1 mm | 6870 | 6.051 kWh/m | trenzado | 3LN | por metro | 40393910037425 | |
18699600BZ
|
(N)HXCH FE180 E30-E60 4 x 150/70 | 6813 | B2ca-s1a,d1,a1 | anaranjado | 4 | 150/70 | 54.3 mm | 8407 | 6.971 kWh/m | trenzado | 3LN | por metro | 40393910037418 | |
18699700BZ
|
(N)HXCH FE180 E30-E60 4 x 185/95 | 8499 | B2ca-s1a,d1,a1 | anaranjado | 4 | 185/95 | 59.8 mm | 10480 | 9.075 kWh/m | trenzado | 3LN | por metro | 40393910037401 | |
18699800BZ
|
(N)HXCH FE180 E30-E60 4 x 240/120 | 10985 | B2ca-s1a,d1,a1 | anaranjado | 4 | 240/120 | 67.9 mm | 13611 | 11.41 kWh/m | trenzado | 3LN | por metro | 40393910037395 | |
18724402BZ
|
(N)HXCH FE180 E30-E60 7 x 1.5/2.5 | 133 | B2ca-s1b,d1,a1 | anaranjado | 7 | 1.5/2.5 | 16.1 mm | 391 | 0.884 kWh/m | de corrido | 7L | por metro | 40393910037227 |