Regresar a la: Cables de seguridad

(N)HXCH FE180 E90 B2ca

halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E90 in accordance with DIN 4102-12
Reacción al fuego según EN 13501-6

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Concentric conductor: bare copper wire
6 Reinforcing helix: bare copper tape
7 Separator: plastic tape
8 Sheath: FRNC/LSZH

Descripción

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 400V.
Permitted operating temperature at conductor of +90˚C.

  • For use in critical fire safety infrastructure (in compliance with VKF, ASTRA, Tunnels Directive, etc.), particularly in escape routes and emergency lines.
  • Conductor concéntrico Bare copper wires with reinforced helix
  • Conductor Cobre desnudo, sólido o trenzado, IEC 60228 y EN 60228 (VDE 0295)
  • Colores principales CENELEC HD 308 S2, VDE 0293
  • Relleno Compuesto libre de halógenos o cinta plástica
  • Aislamiento Aislamiento doble, reticulado, compuesto especial de Keram de alto rendimiento, VDE 0266 "HXI1"
  • Reacción al fuego (Euroclases) EN 13501-6: B2ca
  • Cero halógeno gases no corrosivos IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
  • Propagación de llamas IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
  • Dispersión de llamas IEC 60332-3-22/-24 Cat. A/C, EN 60332-3-22/-24 Cat. A/C, VDE 0482-332-3-22/-24 Cat. A/C, AREI-RGIE Art.104-F2
  • Densidad de humo IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
  • Integridad del Sistema de Circuito DIN 4102-12, VdS 3423 (Single-core more than 16.0 mm²), AREI-RGIE Art.104-FR2
  • Integridad de circuito (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), VDE 0482-362, AREI-RGIE Art.104-FR1
  • System Circuit Integrity is dependent on installation method.
  • Tensión de prueba a 50 Hz 4000 V
  • Temperatura de instalación -5 °C - +50 °C
  • Temperatura de funcionamiento -45 °C - +90 °C
  • Color de la funda exterior anaranjado
  • Material exterior de la vaina Flame retardant Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 "HM4"
  • Integridad de circuito E90
  • Integridad del aislamiento FE 180
  • Mínimo de flexión durante la instalación (multinúcleo) 12 x D
  • Radio de flexión mínimo permanente (multinúcleo) 12 x D

Documentos

EN DE NL FR CN ES IT
Certificado MPA file-icon Certificado MPA file-icon file-icon file-icon file-icon file-icon
CoC CoC CoC file-icon file-icon file-icon file-icon file-icon file-icon
DAT_VDEApproval_OBJ DAT_VDEApproval_OBJ file-icon file-icon file-icon file-icon file-icon file-icon
Ficha técnica Ficha técnica Ficha técnica Ficha técnica Ficha técnica file-icon Ficha técnica Ficha técnica

Versiones

N° de artículo Inventario Producto Reacción al fuegoColor de la funda exteriorNúmero de núcleosDiámetro [mm2]Diámetro exterior de la vaina [mm]Prop. CU [kg/km]Peso [kg/km]Carga de fuego [kWh/m]ConductorConstrucciónUnidad de embalajeGTIN / EAN
18607100BZ (N)HXCH FE180 E90 3 x 1.5/1.5 B2ca-s1a,d1,a1 anaranjado 3 1.5/1.5 13.2 mm66 247 0.599 kWh/mde corrido 3L por metro 40393910039795
18619500BZ (N)HXCH FE180 E90 3 x 2.5/2.5 B2ca-s1a,d1,a1 anaranjado 3 2.5/2.5 14.1 mm104 305 0.784 kWh/mde corrido 3L por metro 40393910039207
18619700BZ (N)HXCH FE180 E90 3 x 4/4 B2ca-s1a,d1,a1 anaranjado 3 4/4 15.6 mm161 401 0.771 kWh/mde corrido 3L por metro 40393910039184
18727800BZ (N)HXCH FE180 E90 3 x 6/6 B2ca-s1a,d1,a1 anaranjado 3 6/6 16.9 mm240 523 0.921 kWh/mde corrido 3L por metro 40393910037173
17241700BZ (N)HXCH FE180 E90 3 x 35/16 B2ca-s1a,d1,a1 anaranjado 3 35/16 29 mm1190 1944 2.267 kWh/mtrenzado 3L por metro 40393910043600
18740800BZ (N)HXCH FE180 E90 3 x 50/25 B2ca-s1a,d1,a1 anaranjado 3 50/25 32.5 mm1723 2549 2.729 kWh/mtrenzado 3L por metro 40393910036961
18740900BZ (N)HXCH FE180 E90 3 x 70/35 B2ca-s1a,d1,a1 anaranjado 3 70/35 37.6 mm2410 3540 3.542 kWh/mtrenzado 3L por metro 40393910036954
18741000BZ (N)HXCH FE180 E90 3 x 95/50 B2ca-s1a,d1,a1 anaranjado 3 95/50 41.9 mm3296 4604 4.285 kWh/mtrenzado 3L por metro 40393910036947
18741100BZ (N)HXCH FE180 E90 3 x 120/70 B2ca-s1a,d1,a1 anaranjado 3 120/70 45.3 mm4236 5694 5.112 kWh/mtrenzado 3L por metro 40393910036930
18741200BZ (N)HXCH FE180 E90 3 x 150/70 B2ca-s1a,d1,a1 anaranjado 3 150/70 50 mm5100 6919 5.889 kWh/mtrenzado 3L por metro 40393910036923
18607200BZ (N)HXCH FE180 E90 4 x 1.5/1.5 B2ca-s1a,d1,a1 anaranjado 4 1.5/1.5 14.1 mm81 282 0.677 kWh/mde corrido 3LN por metro 40393910039788
18619600BZ (N)HXCH FE180 E90 4 x 2.5/2.5 B2ca-s1a,d1,a1 anaranjado 4 2.5/2.5 15.1 mm128 351 0.754 kWh/mde corrido 3LN por metro 40393910039191
18619800BZ (N)HXCH FE180 E90 4 x 4/4 B2ca-s1a,d1,a1 anaranjado 4 4/4 16.7 mm200 466 0.87 kWh/mde corrido 3LN por metro 40393910039177
18619900BZ (N)HXCH FE180 E90 4 x 6/6 B2ca-s1a,d1,a1 anaranjado 4 6/6 18.1 mm297 614 1.051 kWh/mde corrido 3LN por metro 40393910039160
18620000BZ (N)HXCH FE180 E90 4 x 10/10 B2ca-s1a,d1,a1 anaranjado 4 10/10 20.1 mm504 860 1.25 kWh/mde corrido 3LN por metro 40393910039153
18613100BZ (N)HXCH FE180 E90 4 x 16/16 B2ca-s1a,d1,a1 anaranjado 4 16/16 25.3 mm796 1399 1.772 kWh/mtrenzado 3LN por metro 40393910039764
18613200BZ (N)HXCH FE180 E90 4 x 25/16 B2ca-s1a,d1,a1 anaranjado 4 25/16 28.9 mm1142 1899 2.568 kWh/mtrenzado 3LN por metro 40393910039757
18613300BZ (N)HXCH FE180 E90 4 x 35/16 B2ca-s1a,d1,a1 anaranjado 4 35/16 31.6 mm1526 2382 2.568 kWh/mtrenzado 3LN por metro 40393910039740
18613400BZ (N)HXCH FE180 E90 4 x 50/25 B2ca-s1a,d1,a1 anaranjado 4 50/25 36.7 mm2203 3249 3.374 kWh/mtrenzado 3LN por metro 40393910039733
18613500BZ (N)HXCH FE180 E90 4 x 70/35 B2ca-s1a,d1,a1 anaranjado 4 70/35 41.3 mm3082 4376 4.08 kWh/mtrenzado 3LN por metro 40393910039726
18613600BZ (N)HXCH FE180 E90 4 x 95/50 B2ca-s1a,d1,a1 anaranjado 4 95/50 46.4 mm4208 5737 5.179 kWh/mtrenzado 3LN por metro 40393910039719
18613700BZ (N)HXCH FE180 E90 4 x 120/70 B2ca-s1a,d1,a1 anaranjado 4 120/70 50.1 mm5388 7085 5.858 kWh/mtrenzado 3LN por metro 40393910039702
18613800BZ (N)HXCH FE180 E90 4 x 150/70 B2ca-s1a,d1,a1 anaranjado 4 150/70 55.3 mm6540 8640 7.11 kWh/mtrenzado 3LN por metro 40393910039689
18613900BZ (N)HXCH FE180 E90 4 x 185/95 B2ca-s1a,d1,a1 anaranjado 4 185/95 60.8 mm8159 10737 8.61 kWh/mtrenzado 3LN por metro 40393910039665
18614000BZ (N)HXCH FE180 E90 4 x 240/120 B2ca-s1a,d1,a1 anaranjado 4 240/120 69.2 mm10546 13961 10.885 kWh/mtrenzado 3LN por metro 40393910039658
18607302BZ (N)HXCH FE180 E90 7 x 1.5/2.5 B2ca-s1b,d1,a1 anaranjado 7 1.5/2.5 16.1 mm133 391 0.884 kWh/mde corrido 7L por metro 40393910039771
19109602BZ (N)HXCH FE180 E90 7 x 2.5/2.5 B2ca-s1b,d1,a1 anaranjado 7 2.5/2.5 17.3 mm200 486 0.994 kWh/mde corrido 7L por metro 40393910031782
18741502BZ (N)HXCH FE180 E90 12 x 1.5/2.5 B2ca-s1b,d1,a1 anaranjado 12 1.5/2.5 20.2 mm205.8 591 1.308 kWh/mde corrido 12L por metro 40393910036916