(N)HXCH FE180 E90 B2ca

halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E90 in accordance with DIN 4102-12
Reacción al fuego según EN 13501-6

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Concentric conductor: bare copper wire
6 Reinforcing helix: bare copper tape
7 Separator: plastic tape
8 Sheath: FRNC/LSZH

Descripción

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 400V.
Permitted operating temperature at conductor of +90˚C.
Suitable according to VKF fire protection guideline in escape routes and in tunnels according to Astra guideline 13022.

  • For use in critical fire safety infrastructure (in compliance with VKF, ASTRA, Tunnels Directive, etc.), particularly in escape routes and emergency lines.
  • Conductor Cobre desnudo, sólido o trenzado, IEC 60228 y EN 60228 (VDE 0295)
  • Aislamiento Aislamiento doble, reticulado, compuesto especial de Keram de alto rendimiento, VDE 0266 "HXI1"
  • Relleno Compuesto libre de halógenos o cinta plástica
  • Conductor concéntrico Bare copper wires with reinforced helix
  • Color de la funda exterior anaranjado
  • Integridad de circuito (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutos), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
  • Integridad del Sistema de Circuito DIN 4102-12, VdS 3423 (más de 16,0 mm²), AREI-RGIE Art.104-FR2
  • Reacción al fuego (Euroclases) EN 13501-6: B2ca, EN 50399
  • Densidad de humo EN 61034-1/-2, IEC 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
  • Cero halógeno gases no corrosivos EN 60754-1/-2, IEC 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
  • Propagación de llamas EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
  • Dispersión de llamas EN 60332-3-22/-24, IEC 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Art.104-F2
  • Tensión de prueba a 50 Hz 4000 V
  • Temperatura de instalación -5 °C - +50 °C
  • Temperatura de funcionamiento -45 °C - +90 °C
  • Integridad de circuito E90
  • Integridad del aislamiento FE 180
  • Mínimo de flexión durante la instalación (multinúcleo) 12 x D
  • Radio de flexión mínimo permanente (multinúcleo) 12 x D

Documentos

EN DE NL FR CN ES IT
Certificado MPA file-icon Certificado MPA file-icon file-icon file-icon file-icon file-icon
CoC CoC CoC file-icon file-icon file-icon file-icon file-icon file-icon
DAT_VDEApproval_OBJ DAT_VDEApproval_OBJ file-icon file-icon file-icon file-icon file-icon file-icon
Ficha técnica Ficha técnica Ficha técnica Ficha técnica Ficha técnica file-icon Ficha técnica Ficha técnica

Versiones

N° de artículo Inventario Producto Reacción al fuegoColor de la funda exteriorNúmero de núcleosDiámetro [mm2]Diámetro exterior de la vaina [mm]Prop. CU [kg/km]Peso [kg/km]Carga de fuego [kWh/m]ConductorConstrucciónUnidad de embalajeGTIN / EAN
18607100BZ (N)HXCH FE180 E90 3 x 1.5/1.5 B2ca-s1a,d1,a1 anaranjado 3 1.5/1.5 13.2 66 246 0.599 kWh/mde corrido 3L por metro 40393910039795
18619500BZ (N)HXCH FE180 E90 3 x 2.5/2.5 B2ca-s1a,d1,a1 anaranjado 3 2.5/2.5 14.1 104 303 0.784 kWh/mde corrido 3L por metro 40393910039207
18619700BZ (N)HXCH FE180 E90 3 x 4/4 B2ca-s1a,d1,a1 anaranjado 3 4/4 15.6 161 400 0.771 kWh/mde corrido 3L por metro 40393910039184
18727800BZ (N)HXCH FE180 E90 3 x 6/6 B2ca-s1a,d1,a1 anaranjado 3 6/6 16.9 240 521 0.921 kWh/mde corrido 3L por metro 40393910037173
17241700BZ (N)HXCH FE180 E90 3 x 35/16 B2ca-s1a,d1,a1 anaranjado 3 35/16 29 1190 1941 2.267 kWh/mtrenzado 3L por metro 40393910043600
18740800BZ (N)HXCH FE180 E90 3 x 50/25 B2ca-s1a,d1,a1 anaranjado 3 50/25 32.5 1723 2545 2.729 kWh/mtrenzado 3L por metro 40393910036961
18740900BZ (N)HXCH FE180 E90 3 x 70/35 B2ca-s1a,d1,a1 anaranjado 3 70/35 37.6 2410 3536 3.542 kWh/mtrenzado 3L por metro 40393910036954
18741000BZ (N)HXCH FE180 E90 3 x 95/50 B2ca-s1a,d1,a1 anaranjado 3 95/50 41.9 3296 4598 4.285 kWh/mtrenzado 3L por metro 40393910036947
18741100BZ (N)HXCH FE180 E90 3 x 120/70 B2ca-s1a,d1,a1 anaranjado 3 120/70 45.3 4236 5688 5.112 kWh/mtrenzado 3L por metro 40393910036930
18741200BZ (N)HXCH FE180 E90 3 x 150/70 B2ca-s1a,d1,a1 anaranjado 3 150/70 50 5100 6911 5.889 kWh/mtrenzado 3L por metro 40393910036923
18607200BZ (N)HXCH FE180 E90 4 x 1.5/1.5 B2ca-s1a,d1,a1 anaranjado 4 1.5/1.5 14.1 81 280 0.677 kWh/mde corrido 3LN por metro 40393910039788
18619600BZ (N)HXCH FE180 E90 4 x 2.5/2.5 B2ca-s1a,d1,a1 anaranjado 4 2.5/2.5 15.1 128 350 0.754 kWh/mde corrido 3LN por metro 40393910039191
18619800BZ (N)HXCH FE180 E90 4 x 4/4 B2ca-s1a,d1,a1 anaranjado 4 4/4 16.7 200 464 0.87 kWh/mde corrido 3LN por metro 40393910039177
18619900BZ (N)HXCH FE180 E90 4 x 6/6 B2ca-s1a,d1,a1 anaranjado 4 6/6 18.1 297 612 1.051 kWh/mde corrido 3LN por metro 40393910039160
18620000BZ (N)HXCH FE180 E90 4 x 10/10 B2ca-s1a,d1,a1 anaranjado 4 10/10 20.1 504 858 1.25 kWh/mde corrido 3LN por metro 40393910039153
18613100BZ (N)HXCH FE180 E90 4 x 16/16 B2ca-s1a,d1,a1 anaranjado 4 16/16 25.3 796 1396 1.772 kWh/mtrenzado 3LN por metro 40393910039764
18613200BZ (N)HXCH FE180 E90 4 x 25/16 B2ca-s1a,d1,a1 anaranjado 4 25/16 28.9 1142 1895 2.568 kWh/mtrenzado 3LN por metro 40393910039757
18613300BZ (N)HXCH FE180 E90 4 x 35/16 B2ca-s1a,d1,a1 anaranjado 4 35/16 31.6 1526 2378 2.568 kWh/mtrenzado 3LN por metro 40393910039740
18613400BZ (N)HXCH FE180 E90 4 x 50/25 B2ca-s1a,d1,a1 anaranjado 4 50/25 36.7 2203 3245 3.374 kWh/mtrenzado 3LN por metro 40393910039733
18613500BZ (N)HXCH FE180 E90 4 x 70/35 B2ca-s1a,d1,a1 anaranjado 4 70/35 41.3 3082 4371 4.08 kWh/mtrenzado 3LN por metro 40393910039726
18613600BZ (N)HXCH FE180 E90 4 x 95/50 B2ca-s1a,d1,a1 anaranjado 4 95/50 46.4 4208 5731 5.179 kWh/mtrenzado 3LN por metro 40393910039719
18613700BZ (N)HXCH FE180 E90 4 x 120/70 B2ca-s1a,d1,a1 anaranjado 4 120/70 50.1 5388 7078 5.858 kWh/mtrenzado 3LN por metro 40393910039702
18613800BZ (N)HXCH FE180 E90 4 x 150/70 B2ca-s1a,d1,a1 anaranjado 4 150/70 55.3 6540 8631 7.11 kWh/mtrenzado 3LN por metro 40393910039689
18613900BZ (N)HXCH FE180 E90 4 x 185/95 B2ca-s1a,d1,a1 anaranjado 4 185/95 60.8 8159 10727 8.61 kWh/mtrenzado 3LN por metro 40393910039665
18614000BZ (N)HXCH FE180 E90 4 x 240/120 B2ca-s1a,d1,a1 anaranjado 4 240/120 69.2 10546 13949 10.885 kWh/mtrenzado 3LN por metro 40393910039658
18607302BZ (N)HXCH FE180 E90 7 x 1.5/2.5 B2ca-s1b,d1,a1 anaranjado 7 1.5/2.5 16.1 133 390 0.884 kWh/mde corrido 7L por metro 40393910039771
19109602BZ (N)HXCH FE180 E90 7 x 2.5/2.5 B2ca-s1b,d1,a1 anaranjado 7 2.5/2.5 17.3 200 484 0.994 kWh/mde corrido 7L por metro 40393910031782
18741502BZ (N)HXCH FE180 E90 12 x 1.5/2.5 B2ca-s1b,d1,a1 anaranjado 12 1.5/2.5 20.2 205.8 589 1.308 kWh/mde corrido 12L por metro 40393910036916