(N)HXCH FE180 E90 B2ca

Safety cable, 0.6/1kV, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E90 in accordance with DIN 4102-12
Reaction to fire according to EN 13501-6

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Concentric conductor: bare copper wire
6 Reinforcing helix: bare copper tape
7 Separator: plastic tape
8 Sheath: FRNC/LSZH

Description

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 400V.
Permitted operating temperature at conductor of +90˚C.

  • For use in critical fire safety infrastructure (in compliance with VKF, ASTRA, Tunnels Directive, etc.), particularly in escape routes and emergency lines.
  • Concentric conductor Bare copper wires with reinforced helix
  • Conductor Bare copper, solid or stranded, IEC 60228 and EN 60228 (VDE 0295)
  • Core colours CENELEC HD 308 S2, VDE 0293
  • Filler Halogen-free compound or plastic tape
  • Insulation Double insulation, cross-linked, high-performance Keram special compound, VDE 0266 "HXI1"
  • Test voltage at 50Hz 4000 V
  • Installation temperature -5 °C - +50 °C
  • Operating temperature -45 °C - +90 °C
  • Outer sheath colour orange
  • Outer sheath material Flame retardant Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 "HM4"
  • Circuit Integrity E90
  • Insulation integrity FE 180
  • Minimum bending during installation (multi core) 12 x D
  • Minimum bending radius permanent (multi core) 12 x D
  • System Circuit Integrity is dependent on installation method.
  • Reaction to fire (Euroclasses) EN 13501-6: B2ca
  • Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
  • Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
  • Flame spread IEC 60332-3-22/-24 Cat. A/C, EN 60332-3-22/-24 Cat. A/C, VDE 0482-332-3-22/-24 Cat. A/C, AREI-RGIE Art.104-F2
  • Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
  • System circuit integrity DIN 4102-12, VdS 3423 (Single-core more than 16.0 mm²), AREI-RGIE Art.104-FR2
  • Insulation Integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), VDE 0482-362, AREI-RGIE Art.104-FR1

Documentation

EN DE NL FR CN ES IT
CoC CoC CoC file-icon file-icon file-icon file-icon file-icon file-icon
Datasheet Datasheet Datasheet Datasheet Datasheet file-icon Datasheet Datasheet
MPA Certificate file-icon MPA Certificate file-icon file-icon file-icon file-icon file-icon
VDE Certificate VDE Certificate file-icon file-icon file-icon file-icon file-icon file-icon

Versions

Article No. Stock Product Reaction to fireOuter sheath colourNumber of CoresDiameter mm²Outer sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]ConductorConstructionPacking unitGTIN / EAN
18607100BZ (N)HXCH FE180 E90 3 x 1.5/1.5 B2ca-s1a,d1,a1 orange 3 1.5/1.5 13.2 mm66 247 0.599 kWh/msolid 3L by the metre 40393910039795
18619500BZ (N)HXCH FE180 E90 3 x 2.5/2.5 B2ca-s1a,d1,a1 orange 3 2.5/2.5 14.1 mm104 305 0.784 kWh/msolid 3L by the metre 40393910039207
18619700BZ (N)HXCH FE180 E90 3 x 4/4 B2ca-s1a,d1,a1 orange 3 4/4 15.6 mm161 401 0.771 kWh/msolid 3L by the metre 40393910039184
18727800BZ (N)HXCH FE180 E90 3 x 6/6 B2ca-s1a,d1,a1 orange 3 6/6 16.9 mm240 523 0.921 kWh/msolid 3L by the metre 40393910037173
17241700BZ (N)HXCH FE180 E90 3 x 35/16 B2ca-s1a,d1,a1 orange 3 35/16 29 mm1190 1944 2.267 kWh/mstranded 3L by the metre 40393910043600
18740800BZ (N)HXCH FE180 E90 3 x 50/25 B2ca-s1a,d1,a1 orange 3 50/25 32.5 mm1723 2549 2.729 kWh/mstranded 3L by the metre 40393910036961
18740900BZ (N)HXCH FE180 E90 3 x 70/35 B2ca-s1a,d1,a1 orange 3 70/35 37.6 mm2410 3540 3.542 kWh/mstranded 3L by the metre 40393910036954
18741000BZ (N)HXCH FE180 E90 3 x 95/50 B2ca-s1a,d1,a1 orange 3 95/50 41.9 mm3296 4604 4.285 kWh/mstranded 3L by the metre 40393910036947
18741100BZ (N)HXCH FE180 E90 3 x 120/70 B2ca-s1a,d1,a1 orange 3 120/70 45.3 mm4236 5694 5.112 kWh/mstranded 3L by the metre 40393910036930
18741200BZ (N)HXCH FE180 E90 3 x 150/70 B2ca-s1a,d1,a1 orange 3 150/70 50 mm5100 6919 5.889 kWh/mstranded 3L by the metre 40393910036923
18607200BZ (N)HXCH FE180 E90 4 x 1.5/1.5 B2ca-s1a,d1,a1 orange 4 1.5/1.5 14.1 mm81 282 0.677 kWh/msolid 3LN by the metre 40393910039788
18619600BZ (N)HXCH FE180 E90 4 x 2.5/2.5 B2ca-s1a,d1,a1 orange 4 2.5/2.5 15.1 mm128 351 0.754 kWh/msolid 3LN by the metre 40393910039191
18619800BZ (N)HXCH FE180 E90 4 x 4/4 B2ca-s1a,d1,a1 orange 4 4/4 16.7 mm200 466 0.87 kWh/msolid 3LN by the metre 40393910039177
18619900BZ (N)HXCH FE180 E90 4 x 6/6 B2ca-s1a,d1,a1 orange 4 6/6 18.1 mm297 614 1.051 kWh/msolid 3LN by the metre 40393910039160
18620000BZ (N)HXCH FE180 E90 4 x 10/10 B2ca-s1a,d1,a1 orange 4 10/10 20.1 mm504 860 1.25 kWh/msolid 3LN by the metre 40393910039153
18613100BZ (N)HXCH FE180 E90 4 x 16/16 B2ca-s1a,d1,a1 orange 4 16/16 25.3 mm796 1399 1.772 kWh/mstranded 3LN by the metre 40393910039764
18613200BZ (N)HXCH FE180 E90 4 x 25/16 B2ca-s1a,d1,a1 orange 4 25/16 28.9 mm1142 1899 2.568 kWh/mstranded 3LN by the metre 40393910039757
18613300BZ (N)HXCH FE180 E90 4 x 35/16 B2ca-s1a,d1,a1 orange 4 35/16 31.6 mm1526 2382 2.568 kWh/mstranded 3LN by the metre 40393910039740
18613400BZ (N)HXCH FE180 E90 4 x 50/25 B2ca-s1a,d1,a1 orange 4 50/25 36.7 mm2203 3249 3.374 kWh/mstranded 3LN by the metre 40393910039733
18613500BZ (N)HXCH FE180 E90 4 x 70/35 B2ca-s1a,d1,a1 orange 4 70/35 41.3 mm3082 4376 4.08 kWh/mstranded 3LN by the metre 40393910039726
18613600BZ (N)HXCH FE180 E90 4 x 95/50 B2ca-s1a,d1,a1 orange 4 95/50 46.4 mm4208 5737 5.179 kWh/mstranded 3LN by the metre 40393910039719
18613700BZ (N)HXCH FE180 E90 4 x 120/70 B2ca-s1a,d1,a1 orange 4 120/70 50.1 mm5388 7085 5.858 kWh/mstranded 3LN by the metre 40393910039702
18613800BZ (N)HXCH FE180 E90 4 x 150/70 B2ca-s1a,d1,a1 orange 4 150/70 55.3 mm6540 8640 7.11 kWh/mstranded 3LN by the metre 40393910039689
18613900BZ (N)HXCH FE180 E90 4 x 185/95 B2ca-s1a,d1,a1 orange 4 185/95 60.8 mm8159 10737 8.61 kWh/mstranded 3LN by the metre 40393910039665
18614000BZ (N)HXCH FE180 E90 4 x 240/120 B2ca-s1a,d1,a1 orange 4 240/120 69.2 mm10546 13961 10.885 kWh/mstranded 3LN by the metre 40393910039658
18607302BZ (N)HXCH FE180 E90 7 x 1.5/2.5 B2ca-s1b,d1,a1 orange 7 1.5/2.5 16.1 mm133 391 0.884 kWh/msolid 7L by the metre 40393910039771
19109602BZ (N)HXCH FE180 E90 7 x 2.5/2.5 B2ca-s1b,d1,a1 orange 7 2.5/2.5 17.3 mm200 486 0.994 kWh/msolid 7L by the metre 40393910031782
18741502BZ (N)HXCH FE180 E90 12 x 1.5/2.5 B2ca-s1b,d1,a1 orange 12 1.5/2.5 20.2 mm205.8 591 1.308 kWh/msolid 12L by the metre 40393910036916
Additional dimensions available on request.