Back to: Safety cables

JE-H(St)HRH...Bd FE180 E30-E90 fire alarm, black

Fire alarm cable with steel wire braiding, max. 225V, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30-E90* in accordance with DIN 4102-12

1 Conductor: solid
2 Insulation: cross-linked polymer, halogen-free
3 Drain wire: copper, Ø 0.8 mm
4 Inner covering: plastic tape, halogen-free
5 Shielding: Al-laminated plastic foil, halogen-free
6 Inner sheath: FRNC/LS0H
7 Armouring: galvanised steel wire band
8 Sheath: FRNC/LS0H

Description

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor and outdoor applications. The steel wire braiding serves as mechanical protection. The fire alarm cables correspond to the demands of System Circuit Integrity E30-E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 110V.
Permitted operating temperature at conductor of +70°C.

  • Conductor Bare copper, solid, 0.8 mm diameter, VDE 0815
  • Insulation Fire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-36
  • Core colours VDE 0815
  • Shielding Al-laminated tape with copper drain wire Ø 0.8 mm
  • Inner sheath Flame retardant polyolefin compound, VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM2"
  • Armouring (rodent protection) Galvanised steel wire braid
  • Outer sheath material Flame retardant polyolefin compound VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM 2"
  • Capacitive coupling 0,8 mm, 100m @ 800Hz 200 pF/km
  • Maximum loop resistance 0,8 mm 73.2 Ω/km
  • Minimum insulation resistance 100 MΩ x km
  • operating capacity, 1km @ 800Hz 120 nF/km
  • peak voltage 225 V
  • Test voltage 50Hz, core/core 500 V
  • Test voltage 50Hz, core/screen 2000 V
  • Installation temperature -5 °C - +50 °C
  • Operating temperature -30 °C - +70 °C
  • Circuit Integrity E90
  • Insulation integrity FE 180
  • Minimal crush resistance / 10cm 1000 N
  • Minimum bending during installation (multi core) 7.5 x D
  • Minimum bending radius permanent (multi core) 7.5 x D
  • System Circuit Integrity dependent on installation method.
  • Insulation Integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
  • System circuit integrity DIN 4102-12, AREI-RGIE Art.104-FR2
  • Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
  • Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
  • Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
  • Flame spread IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Art.104-F2

Documentation

EN DE NL FR CN ES IT
Datasheet Datasheet Datasheet Datasheet Datasheet file-icon Datasheet Datasheet
MPA Certificate file-icon MPA Certificate file-icon file-icon file-icon file-icon file-icon

Versions

Article No. Stock Product Outer sheath colourNumber of pairsNumber of CoresDiameter mmOuter sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]Packing unitGTIN / EAN
191071 JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 2x2x0.8 mm black 2 2 0.8 9.3 25 125 0.26 kWh/mby the metre 40393910069945
191554 JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 4x2x0.8 mm black 4 2 0.8 12 45 194 0.39 kWh/mby the metre 40393910069211
194070 JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 8x2x0.8 mm black 8 2 0.8 18.2 85 419 0.93 kWh/mby the metre 40393910064759
196354 JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 12x2x0.8 mm black 12 2 0.8 19.1 126 490 1.01 kWh/mby the metre 40393910061192
191070 JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 16x2x0.8 mm black 16 2 0.8 20.5 166 557 1.17 kWh/mby the metre 40393910069952
196265 JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 20x2x0.8 mm black 20 2 0.8 22.3 206 680 1.32 kWh/mby the metre 40393910061536
196347 JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 32x2x0.8 mm black 32 2 0.8 26.7 326 912 1.72 kWh/mby the metre 40393910061222
Additional dimensions available on request.