Back to: Safety cables

FE180 E30

Safety cable, 0.6/1kV, Keram
halogen-free, with improved fire characteristics,
in accordance to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H
30 minutes system circuit integrity* with reference to DIN 4102-12

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Sheath: FRNC/LSZH

Description

Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.

  • Outer sheath material Compound, HD 604 S1 part 5 H
  • Conductor Bare copper, solid or stranded, IEC 60228 and EN 60228 (≥16 mm2: VDE 0295)
  • Core colours CENELEC HD 308 S2
  • Filler HD 604 S1 part 5 H
  • Insulation Special compound, HD 604 S1 part 5 H
  • Test voltage at 50Hz 3500 V
  • Installation temperature -5 °C - +50 °C
  • Operating temperature -45 °C - +90 °C
  • Circuit Integrity E30
  • Insulation integrity FE 180
  • Minimum bending during installation (multi core) 12 x D
  • Minimum bending during installation (single core) 15 x D
  • Minimum bending radius permanent (multi core) 12 x D
  • Minimum bending radius permanent (single core) 15 x D
  • Remarks bending radius 50% reduction if installation at 30°C and with a template
  • System Circuit Integrity is depemndent on installation method.
  • Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA, SEV TPV11
  • Flame Propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1, SEV TP 20B/3C 3.4.1.1
  • Flame Spread IEC 60332-3-24 Cat. C, EN 60332-3-24 Cat. C, VDE 0482-332-3-24 Cat. C, AREI-RGIE Art.104-F2, SEV TP 20B/3C 3.4.1.3
  • Smoke Density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD, SEV TP 20B/3C 3.4.3
  • Circuit Integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), VDE 0482-362, AREI-RGIE Art.104-FR1

Documentation

EN DE NL FR CN ES IT
Datasheet Datasheet Datasheet Datasheet Datasheet file-icon Datasheet Datasheet

Versions

Article No. Stock Product Number of CoresDiameter mm²Outer sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]ConductorConstructionGTIN
191118 FE180 E30 2 x 1.5 2 1.5 7.8 29 102 0.22 kWh/msolid LN 40393910069662
188360 FE180 E30 2 x 1,5 2 1.5 7.8 29 102 0.22 kWh/msolid 2L 40393910072242
191119 FE180 E30 2 x 2.5 2 2.5 9 48 142 0.28 kWh/msolid LN 40393910069655
190402 FE180 E30 2 x 2,5 2 2.5 9 48 142 0.28 kWh/msolid 2L 40393910070996
187180 FE180 E30 3 x 1.5 3 1.5 8.3 43 121 0.25 kWh/msolid LNPE 40393910074499
187184 FE180 E30 3 x 2.5 3 2.5 9.5 72 169 0.31 kWh/msolid LNPE 40393910074451
187187 FE180 E30 3 x 4 3 4 11 115 243 0.41 kWh/msolid LNPE 40393910074420
187189 FE180 E30 3 x 6 3 6 12.5 173 329 0.51 kWh/msolid LNPE 40393910074406
187182 FE180 E30 4 x 1.5 4 1.5 9.1 58 147 0.29 kWh/msolid 3LPE 40393910074475
190502 FE180 E30 4 x 2.5 4 2.5 10.5 96 209 0.38 kWh/msolid 3LPE 40393910070828
192352 FE180 E30 4 x 4 4 4 12.2 154 304 0.49 kWh/msolid 3LPE 40393910067705
192353 FE180 E30 4 x 6 4 6 13.8 230 409 0.61 kWh/msolid 3LPE 40393910067699
187183 FE180 E30 5 x 1.5 5 1.5 9.9 72 177 0.35 kWh/msolid 3LNPE 40393910074468
187186 FE180 E30 5 x 2.5 5 2.5 11.6 120 255 0.47 kWh/msolid 3LNPE 40393910074437
187188 FE180 E30 5 x 4 5 4 13.4 192 371 0.61 kWh/msolid 3LNPE 40393910074413
187190 FE180 E30 5 x 6 5 6 15.2 288 504 0.76 kWh/msolid 3LNPE 40393910074390
186267 FE180 E30 7 x 1.5 7 1.5 10.8 100.8 220 0.41 kWh/msolid 6LPE 40393910076172
186268 FE180 E30 7 x 2.5 7 2.5 12.5 168 319 0.53 kWh/msolid 6LPE 40393910076165
187201 FE180 E30 7 x 6 7 6 16.7 403 644 0.89 kWh/msolid 6LPE 40393910074338
187108 FE180 E30 8 x 1.5 8 1.5 11.9 115 258 0.48 kWh/msolid 7LPE 40393910074680
188345 FE180 E30 10 x 1.5 10 1.5 13.8 144 319 0.69 kWh/msolid 9LPE 40393910072372
186269 FE180 E30 12 x 1.5 12 1.5 14.2 172.8 364 0.66 kWh/msolid 11LPE 40393910076158
192479 FE180 E30 12 x 2.5 12 2.5 16.7 288 536 0.88 kWh/msolid 11LPE 40393910067354
187109 FE180 E30 21 x 1.5 21 1.5 17.7 303 578 0.99 kWh/msolid 20LPE 40393910074673
190412 FE180 E30 27 x 1.5 27 1.5 20.4 389 752 1.30 kWh/msolid 26LPE 40393910070972
Additional dimensions available on request.