Back to: Safety cables

JE-H(St)H...Bd FE180 E30-E90 fire alarm

Fire alarm cable, max. 225V, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30-E90* in accordance with DIN 4102-12

1 Conductor: solid
2 Insulation: cross-linked polymer, zero halogen
3 Drain wire: Ø 0.8 mm
4 Separator: plastic tape, zero halogen
5 Shielding: Al-laminated tape, zero halogen
6 Sheath: FRNC/LSZH

Description

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E30-E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 110V.
Permitted operating temperature at conductor of +70˚C.

  • Conductor Bare copper, solid, 0.8 mm diameter, VDE 0815
  • Insulation Fire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-36
  • Core colours VDE 0815
  • Shielding Al-laminated tape with copper drain wire Ø 0.8 mm
  • Outer sheath material Flame retardant polyolefin compound VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM 2"
  • Capacitive coupling 0,8 mm, 100m @ 800Hz 200 pF/km
  • Maximum loop resistance 0,8 mm 73.2 Ω/km
  • Minimum insulation resistance 100 MΩ x km
  • operating capacity, 1km @ 800Hz 120 nF/km
  • peak voltage 225 V
  • Test voltage 50Hz, core/core 500 V
  • Test voltage 50Hz, core/screen 2000 V
  • Installation temperature -5 °C - +50 °C
  • Operating temperature -30 °C - +70 °C
  • Circuit Integrity E90
  • Insulation integrity FE 180
  • Minimal crush resistance / 10cm 1000 N
  • Minimum bending during installation (multi core) 7.5 x D
  • Minimum bending radius permanent (multi core) 7.5 x D
  • System Circuit Integrity is dependent on installation method.
  • Insulation Integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), NBN 713-020 (Rf 1 1/2), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
  • System circuit integrity DIN 4102-12, AREI-RGIE Art.104-FR2
  • Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
  • Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
  • Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
  • Flame spread IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Art.104-F2

Documentation

EN DE NL FR CN ES IT
Datasheet Datasheet Datasheet Datasheet Datasheet file-icon Datasheet Datasheet
MPA Certificate file-icon MPA Certificate file-icon file-icon file-icon file-icon file-icon
VDE Certificate file-icon VDE Certificate file-icon file-icon file-icon file-icon file-icon

Versions

Article No. Stock Product Outer sheath colourNumber of pairsNumber of CoresDiameter mmOuter sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]Packing unitGTIN / EAN
188093 JE-H(St)H...Bd FE180 E30-E90 fire alarm 1x2x0.8 mm red 1 2 0.8 5.6 15 42 0.095 kWh/mby the metre 40393910073164
188098 JE-H(St)H...Bd FE180 E30-E90 fire alarm 2x2x0.8 mm red 2 2 0.8 6.3 25 59 0.123 kWh/mby the metre 40393910073126
188101 JE-H(St)H...Bd FE180 E30-E90 fire alarm 4x2x0.8 mm red 4 2 0.8 9 45 101 0.21 kWh/mby the metre 40393910073102
188103 JE-H(St)H...Bd FE180 E30-E90 fire alarm 8x2x0.8 mm red 8 2 0.8 13.9 85 221 0.52 kWh/mby the metre 40393910073089
188105 JE-H(St)H...Bd FE180 E30-E90 fire alarm 12x2x0.8 mm red 12 2 0.8 14.8 126 281 0.58 kWh/mby the metre 40393910073065
188109 JE-H(St)H...Bd FE180 E30-E90 fire alarm 20x2x0.8 mm red 20 2 0.8 18.8 206 421 0.80 kWh/mby the metre 40393910073027
188107 JE-H(St)H...Bd FE180 E30-E90 fire alarm 16x2x0.8 mm red 16 2 0.8 16.6 166 325 0.69 kWh/mby the metre 40393910073041
188112 JE-H(St)H...Bd FE180 E30-E90 fire alarm 32x2x0.8 mm red 32 2 0.8 22 326 589 1.02 kWh/mby the metre 40393910072990
188114 JE-H(St)H...Bd FE180 E30-E90 fire alarm 40x2x0.8 mm red 40 2 0.8 25.5 407 761 1.38 kWh/mby the metre 40393910072976
188116 JE-H(St)H...Bd FE180 E30-E90 fire alarm 52x2x0.8 mm red 52 2 0.8 27.8 529 933 1.59 kWh/mby the metre 40393910072952
Additional dimensions available on request.