JE-H(St)H...Bd FE180 E30 L
Wiring cable for industrial electronics, max. 225V, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30 in accordance with DIN 4102-12
1 Conductor: solid
2 Insulation: cross-linked polymer, zero halogen
3 Drain wire: Ø 0.8 mm
4 Separator: plastic tape, zero halogen
5 Shielding: Al-laminated tape, zero halogen
6 Sheath: FRNC/LSZH






Description
Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E30* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 110V.
Permitted operating temperature at conductor of +70˚C.
- Conductor Bare copper, solid, 0.8 mm diameter, VDE 0815
- Insulation Fire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-36
- Core colours VDE 0815
- Shielding Al-laminated tape with copper drain wire Ø 0.8 mm
- Outer sheath material Flame retardant polyolefin compound VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM 2"
- Capacitive coupling 0,8 mm, 100m @ 800Hz 200 pF/km
- Maximum loop resistance 0,8 mm 73.2 Ω/km
- Minimum insulation resistance 100 MΩ x km
- operating capacity, 1km @ 800Hz 120 nF/km
- peak voltage 225 V
- Test voltage 50Hz, core/core 500 V
- Test voltage 50Hz, core/screen 2000 V
- Installation temperature -5 °C - +50 °C
- Operating temperature -30 °C - +70 °C
- Circuit Integrity E30
- Insulation integrity FE 180
- Minimal crush resistance / 10cm 1000 N
- Minimum bending during installation (multi core) 7.5 x D
- Minimum bending radius permanent (multi core) 7.5 x D
- System Circuit Integrity is dependent on installation method.
- Insulation Integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), NBN 713-020, VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
- System circuit integrity DIN 4102-12, AREI-RGIE Art.104-FR2
- Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
- Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
- Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
- Flame spread IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Art.104-F2
Documentation
Versions
Article No. | Stock | Product | CU rate (AT) | Outer sheath colour | Number of pairs | Number of Cores | Diameter mm | Outer sheath diameter [mm] | Weight [kg/km] | Fire load [kWh/m] | Packing unit | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|---|---|
188376
|
JE-H(St)H...Bd FE180 E30 L 1x2x0.8 mm | 15 | orange | 1 | 2 | 0.8 | 5.6 | 42 | 0.095 kWh/m | by the metre | 40393910072150 | |
18831800ZK
|
JE-H(St)H...Bd FE180 E30 L 2x2x0.8 mm | 25 | orange | 2 | 2 | 0.8 | 6.1 | 57 | 0.123 kWh/m | 1000 m drum | 40393910035292 | |
18831800ZL
|
JE-H(St)H...Bd FE180 E30 L 2x2x0.8 mm | 25 | orange | 2 | 2 | 0.8 | 6.1 | 57 | 0.123 kWh/m | 500 m drum | 40393910035285 | |
18831800ZZ
|
JE-H(St)H...Bd FE180 E30 L 2x2x0.8 mm | 25 | orange | 2 | 2 | 0.8 | 6.1 | 59 | 0.123 kWh/m | by the metre | 40393910035278 | |
188325
|
JE-H(St)H...Bd FE180 E30 L 4x2x0.8 mm | 45 | orange | 4 | 2 | 0.8 | 9 | 102 | 0.21 kWh/m | by the metre | 40393910072440 |