Back to: Safety cables





Enhanced Fire Safety Cable solid
Fire alarm cable, 300/500V
halogen-free, with improved fire characteristics,
BS 7629-1 and BS 5839-1 Enhanced
1 Conductor: solid
2 Insulation: fire resistant special compound (BS 7655)
3 Drain wire: tinned copper
4 Inner covering: glass fibre tape
5 Shielding: Al-laminated tape
6 Sheath: FRNC/LSZH






Description
Cable for fire alarm systems and emergency lighting for permament installation in buildings.
Permitted operating temperature at conductor of +90˚C.
- Conductor Bare copper, solid, IEC 60228 and EN 60228
- Core colours 2 cores + earth: blue, brown (Installation only according to BS 7671 – blue neutral, brown phase)
- Inner covering Glass fibre tape
- Insulation Special compound, BS EN 50363-5
- Shielding Al-laminated tape and tinned copper drain wire; IEC 60228, EN 60228
- Test voltage at 50Hz 2000 V
- Installation temperature -5 °C - +50 °C
- Operating temperature -15 °C - +90 °C
- Outer sheath material Polyolefin compound, BS 7655-6.1, LTS3
- Circuit Integrity No
- Insulation integrity PH 120
- Minimum bending during installation (multi core) 6 x D
- Minimum bending radius permanent (multi core) 6 x D
- Additional dimensions available on request.
- Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
- Flame Propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
- Flame Spread IEC 60332-3-22/-24 Cat. A/C, EN 60332-3-22/-24 Cat. A/C, VDE 0482-332-3-22/-24 Cat. A/C, AREI-RGIE Art.104-F2
- Smoke Density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
- Insulation Integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-2 (120 minutes), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1, BS 8434-2, BS EN 50200
Documentation
Versions
Article No. | Stock | Product | Outer sheath colour | Number of Cores | Diameter mm² | Outer sheath diameter [mm] | CU rate [kg/km] | Resistance [Ω/km] | Voltage drop [Ω mV/A/m] | Weight [kg/km] | Fire load [kWh/m] | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|---|---|
188368
|
Enhanced Fire Safety Cable | red | 2 | 1.5 | 8.3 mm | 43 | 12.1 | 29 Ω mV/A/m | 98 | 0.19 kWh/m | 40393910072228 | |
188369
|
Enhanced Fire Safety Cable | white | 2 | 1.5 | 8.3 mm | 43 | 12.1 | 29 Ω mV/A/m | 98 | 0.19 kWh/m | 40393910072211 | |
188370
|
Enhanced Fire Safety Cable | red | 2 | 2.5 | 9.7 mm | 72 | 7.41 | 18 Ω mV/A/m | 140 | 0.26 kWh/m | 40393910072204 | |
188371
|
Enhanced Fire Safety Cable | white | 2 | 2.5 | 9.7 mm | 72 | 7.41 | 18 Ω mV/A/m | 140 | 0.26 kWh/m | 40393910072198 | |
191679
|
Enhanced Fire Safety Cable* | red | 4 | 1.5 | 9.7 mm | 72 | 12.1 | 29 Ω mV/A/m | 151 | 0.28 kWh/m | 40393910068931 |
* not LPCB certified