Back to: Safety cables

FE180 flex

Control cable flex, 300/500V, Keram
halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H

1 Conductor: stranded
2 Fire barrier: high-performance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Sheath: FRNC / LSZH

Description

Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.

  • Outer sheath material Compound, HD 604 S1 part 5 H
  • Conductor Bare copper, stranded, IEC 60228 class 5, EN 60228
  • Core colours CENELEC HD 308 S2
  • Filler HD 604 S1 part 5 H
  • Insulation Special compound, HD 604 S1 part 5 H
  • Test voltage at 50Hz 2000 V
  • Installation temperature -5 °C - +50 °C
  • Operating temperature -45 °C - +90 °C
  • Insulation integrity FE 180
  • Minimum bending during installation (multi core) 6 x D
  • Minimum bending radius permanent (multi core) 4 x D
  • Additional dimensions available on request.
  • Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA, SEV TPV11
  • Flame Propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1, SEV TP 20B/3C 3.4.1.1
  • Flame Spread IEC 60332-3-24 Cat. C, EN 60332-3-24 Cat. C, VDE 0482-332-3-24 Cat. C, AREI-RGIE Art.104-F2, SEV TP 20B/3C 3.4.1.3
  • Smoke Density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD, SEV TP 20B/3C 3.4.3
  • Circuit Integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), VDE 0482-362, AREI-RGIE Art.104-FR1

Documentation

EN DE NL FR CN ES IT
Datasheet Datasheet Datasheet Datasheet Datasheet file-icon Datasheet Datasheet

Versions

Article No. Stock Product Number of CoresDiameter mm²Outer sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]ConstructionGTIN
188335 FE180 flex 3 x 1.5 3 1.5 8.5 43 123 0.27 kWh/mLNPE 40393910072419
187554 FE180 flex 5 x 1.5 5 1.5 10.3 72 182 0.40 kWh/m3LNPE 40393910073645
187179 FE180 flex 5 x 2.5 5 2.5 12.1 120 271 0.55 kWh/m3LNPE 40393910074505
192367 FE180 flex 7 x 1.5 7 1.5 11 101 222 0.44 kWh/m6LPE 40393910067620
185228 FE180 flex 8 x 1.5 8 1.5 12.4 115 273 0.56 kWh/m6LNPE 40393910077315
191059 FE180 flex 12 x 1.5 12 1.5 14 173 313 0.72 kWh/m11LPE 40393910070033
191060 FE180 flex 16 x 1.5 16 1.5 16 231 410 0.89 kWh/m15LPE 40393910070026
191061 FE180 flex 21 x 1.5 21 1.5 18 303 527 1.10 kWh/m20LPE 40393910070019