FO Universal wbGGFR Safety / U-DQ(ZN)BH
Safety cable E30*, up to 60 fibres
metal-free, water resistant, rodent protection,
in accordance with IEC 60332-1-2 and IEC 60332-3-24
30 minutes System Circuit Integrity* with reference to DIN 4102-12
1 ≤ 12 fibres
2 Flame retardant protective coating
3 Glass armour
4 Ripcord
5 FR/LS0H sheath





Description
Metal-free fibre optic safety cable with multiple loose tubes, up to 60 fibres.
The optimal combination of flame retardant fibre coating and flame-inhibiting stabilizing elements ensures enhanced functional integrity (System Circuit Integrity*) in case of fire for 30 minutes (transmission of audio, video and 1Gbit/s signals approved by a certified test report).
-
Safety applications in tunnels, underground railways, banks, insurance companies, large-scale industry.
LAN backbone.
Indoor and outdoor cabling.
Can also be installed in cable platforms, trays, ducts and vertical shafts (without System Circuit Integrity*).
Can be spliced in FO distributors.
- Outer sheath material FRNC/LSZH
- Installation temperature -10 °C - +50 °C
- Storage temperature -25 °C - +70 °C
- Operating temperature -25 °C - +70 °C
- Field of application Universal
- Imprint DATWYLER «cable type» «Datwyler designation» «DIN designation» «no. of fibres» «fibre type» «add. text» «batch no.» «meter marks»
- Maximum number of fibres 72
- * System Circuit Integrity is dependent on installation method. Certified clamps, ducts, conduits, etc. are mandatory.
- Tensile performance IEC 60794-1-21 E1
- Crush resistance IEC 60794-1-21 E3
- Impact IEC 60794-1-21 E4
- Repeated bending IEC 60794-1-21 E6
- Torsion IEC 60794-1-21 E7
- Bend IEC 60794-1-21 E11
- Temperature cycling IEC 60794-1-22 F1
- Water penetration IEC 60794-1-22 F5
- Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2
- Flame Propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
- Flame Spread IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24
- Smoke Density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2
- UV resistance EN 50289-4-17
Documentation
More Information
Versions
Article No. | Stock | Product | Outer sheath colour | Number of Fibres | Fibre type | Outer sheath diameter [mm] | Bending radius [mm] | Weight [kg/km] | Tensile load [N] | Crush resistance short term [N] | Crush resistance continuous [N] | Fire load [kWh/m] | Packing unit | GTIN | Fibre category | Fibres per loose tube | Loose tube construction | Number of used loose tubes |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
194430
|
FO Universal Safety 1x12 | red | 12 | E9/125 G.652.D OS2 | 12.5 mm | 190 mm | 181 | 6000 | 5000 | 3000 | 0.733 kWh/m | by the metre | 40393910064223 | OS2 | 12 | 1 | 1 | |
190223
|
FO Universal Safety 2x12 | red | 24 | E9/125 G.652.D OS2 | 12.5 mm | 190 mm | 181 | 6000 | 5000 | 3000 | 0.733 kWh/m | by the metre | 40393910071238 | OS2 | 12 | 2 | 2 | |
187360
|
FO Universal Safety 2x12 | red | 24 | G50/125 OM3 | 12.5 mm | 190 mm | 181 | 6000 | 5000 | 3000 | 0.733 kWh/m | by the metre | 40393910073904 | OM3 | 12 | 2 | 2 | |
193454
|
FO Universal Safety 2x12 | red | 24 | G50/125 OM4 | 12.5 mm | 190 mm | 181 | 6000 | 5000 | 3000 | 0.733 kWh/m | by the metre | 40393910065466 | OM4 | 12 | 2 | 2 | |
190224
|
FO Universal Safety 3x12 | red | 36 | E9/125 G.652.D OS2 | 12.5 mm | 190 mm | 181 | 6000 | 5000 | 3000 | 0.733 kWh/m | by the metre | 40393910071221 | OS2 | 12 | 3 | 3 | |
193455
|
FO Universal Safety 3x12 | red | 36 | G50/125 OM4 | 12.5 mm | 190 mm | 181 | 6000 | 5000 | 3000 | 0.733 kWh/m | by the metre | 40393910065459 | OM4 | 12 | 3 | 3 | |
194575
|
FO Universal Safety 4x12 | red | 48 | E9/125 G.652.D BLO | 12.5 mm | 190 mm | 181 | 6000 | 5000 | 3000 | 0.733 kWh/m | by the metre | 40393910064063 | OS2 | 12 | 4 | 4 | |
190225
|
FO Universal Safety 4x12 | red | 48 | E9/125 G.652.D OS2 | 12.5 mm | 190 mm | 181 | 6000 | 5000 | 3000 | 0.733 kWh/m | by the metre | 40393910071214 | OS2 | 12 | 4 | 4 | |
191191
|
FO Universal Safety 4x12 | red | 48 | G50/125 OM3 | 12.5 mm | 190 mm | 181 | 6000 | 5000 | 3000 | 0.733 kWh/m | by the metre | 40393910069594 | OM3 | 12 | 4 | 4 | |
193456
|
FO Universal Safety 4x12 | red | 48 | G50/125 OM4 | 12.5 mm | 190 mm | 181 | 6000 | 5000 | 3000 | 0.733 kWh/m | by the metre | 40393910065442 | OM4 | 12 | 4 | 4 | |
190226
|
FO Universal Safety 5x12 | red | 60 | E9/125 G.652.D OS2 | 12.5 mm | 190 mm | 181 | 6000 | 5000 | 3000 | 0.733 kWh/m | by the metre | 40393910071207 | OS2 | 12 | 5 | 5 | |
190605
|
FO Universal Safety 5x12 | red | 60 | G50/125 OM3 | 12.5 mm | 190 mm | 181 | 6000 | 5000 | 3000 | 0.733 kWh/m | by the metre | 40393910070514 | OM3 | 12 | 5 | 5 | |
193457
|
FO Universal Safety 5x12 | red | 60 | G50/125 OM4 | 12.5 mm | 190 mm | 181 | 6000 | 5000 | 3000 | 0.733 kWh/m | by the metre | 40393910065435 | OM4 | 12 | 5 | 5 |