FO Universal ZGGFR Safety / U-DQ(ZN)BH
Safety cable E30*, up to 12 fibres
metal-free, water resistant, rodent protection,
in accordance with IEC 60332-1-2 and IEC 60332-3-24
30 minutes System Circuit Integrity* with reference to DIN 4102-12
1 ≤ 12 fibres
2 Flame retardant protective coating
3 Glass armour
4 Ripcord
5 FR/LS0H sheath





Description
Metal-free fibre optic safety cable with one central loose tube, up to 12 fibres.
The optimal combination of flame retardant fibre coating and flame-inhibiting stabilizing elements ensures enhanced functional integrity (System Circuit Integrity*) in case of fire for 30 minutes (transmission of audio, video and 1Gbit/s signals approved by a certified test report).
-
Safety applications in tunnels, underground railways, banks, insurance companies, large-scale industry.
LAN backbone.
Indoor and outdoor cabling.
Can also be installed in cable platforms, trays, ducts and vertical shafts (without System Circuit Integrity*).
Can be spliced in FO distributors.
- Installation temperature -10 °C - +50 °C
- Storage temperature -25 °C - +70 °C
- Operating temperature -25 °C - +70 °C
- Outer sheath material FRNC/LSZH
- Imprint DATWYLER «cable type» «Datwyler designation» «DIN designation» «no. of fibres» «fibre type» «add. text» «batch no.» «meter marks»
- Circuit Integrity E30
- Field of application Universal
- Maximum number of fibres 12
- * System Circuit Integrity is dependent on installation method. Certified clamps, ducts, conduits, etc. are mandatory.
- Tensile performance IEC 60794-1-21 E1
- Crush resistance IEC 60794-1-21 E3
- Impact IEC 60794-1-21 E4
- Repeated bending IEC 60794-1-21 E6
- Torsion IEC 60794-1-21 E7
- Bend IEC 60794-1-21 E11
- Temperature cycling IEC 60794-1-22 F1
- Water penetration IEC 60794-1-22 F5
- Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2
- Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
- Flame spread IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24
- Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2
- System circuit integrity with reference to DIN 4102-12, VKF Fire Safety Application No. 24176
- UV resistance EN 50289-4-17
- Insulation Integrity (FE180) IEC 60331-11, IEC 60331-25 (FE180), EN 50200 PH30, VDE 0482-200
Documentation
More Information
Versions
Article No. | Stock | Product | Outer sheath colour | Number of fibres | Fibre type | Outer sheath diameter [mm] | Bending radius [mm] | Weight [kg/km] | Tensile load [N] | Crush resistance short term [N] | Crush resistance continuous [N] | Fire load [kWh/m] | Packing unit | GTIN / EAN | Fibre category | Fibres per loose tube | Loose tube construction | Number of used loose tubes |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
187288
|
FO Universal Safety 1x4 | red | 4 | E9/125 G.652.D OS2 | 7.8 | 120 | 75 | 1000 | 5000 | 2000 | 0.301 kWh/m | by the metre | 40393910074024 | OS2 | 4 | 1 | 1 | |
190604
|
FO Universal Safety 1x4 | red | 4 | G50/125 OM3 | 7.8 | 120 | 75 | 1000 | 5000 | 2000 | 0.301 kWh/m | by the metre | 40393910070521 | OM3 | 4 | 1 | 1 | |
193447
|
FO Universal Safety 1x4 | red | 4 | G50/125 OM4 | 7.8 | 120 | 75 | 1000 | 5000 | 2000 | 0.301 kWh/m | by the metre | 40393910065527 | OM4 | 4 | 1 | 1 | |
191867
|
FO Universal Safety 1x6 | red | 6 | E9/125 G.652.D OS2 | 7.8 | 120 | 75 | 1000 | 5000 | 2000 | 0.301 kWh/m | by the metre | 40393910068610 | OS2 | 6 | 1 | 1 | |
191851
|
FO Universal Safety 1x6 | red | 6 | G50/125 OM3 | 7.8 | 120 | 75 | 1000 | 5000 | 2000 | 0.301 kWh/m | by the metre | 40393910068665 | OM3 | 6 | 1 | 1 | |
193448
|
FO Universal Safety 1x6 | red | 6 | G50/125 OM4 | 7.8 | 120 | 75 | 1000 | 5000 | 2000 | 0.301 kWh/m | by the metre | 40393910065510 | OM4 | 6 | 1 | 1 | |
196130
|
FO Universal Safety 1x8 | red | 8 | E9/125 G.652.D OS2 | 7.8 | 120 | 75 | 1000 | 5000 | 2000 | 0.301 kWh/m | by the metre | 40393910061642 | OS2 | 8 | 1 | 1 | |
196120
|
FO Universal Safety 1x8 | red | 8 | G50/125 OM3 | 7.8 | 120 | 75 | 1000 | 5000 | 2000 | 0.301 kWh/m | by the metre | 40393910061659 | OM3 | 8 | 1 | 1 | |
193449
|
FO Universal Safety 1x8 | red | 8 | G50/125 OM4 | 7.8 | 120 | 75 | 1000 | 5000 | 2000 | 0.301 kWh/m | by the metre | 40393910065503 | OM4 | 8 | 1 | 1 | |
190719
|
FO Universal Safety 1x12 | red | 12 | E9/125 G.652.D OS2 | 7.8 | 120 | 75 | 1000 | 5000 | 2000 | 0.301 kWh/m | by the metre | 40393910070361 | OS2 | 12 | 1 | 1 | |
191796
|
FO Universal Safety 1x12 | red | 12 | G50/125 OM3 | 7.8 | 120 | 75 | 1000 | 5000 | 2000 | 0.301 kWh/m | by the metre | 40393910068795 | OM3 | 12 | 1 | 1 | |
193450
|