CU 8203 4P
Data cable, S/FTP, Category 8.2, AWG23, Euroclass Cca
2000 MHz
1 Inner conductor: AWG23 Bare copper wire
2 PE insulated conductor: 1.6 mm ∅
3 Screen (pair): Alu PETP foil
4 Overall screen: Tinned braided copper
5 Outer sheath: FRNC/LSOH Orange RAL 2003












Description
Electrically and mechanically superior quality Cat.8.2 data cable – exceeds the requirements of ISO/IEC 11801, IEC 61156-5, EN 50173-1, EN 50288-12-1 and IEC 61156-9.
Excellent shielding effect due to individually screened pairs and overall copper braid.
Compact cable design.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
-
High-end data cable for data centres.
Developed particularly for 40 GBase-T transmission with maximum channel length of 30 metres in End of Row or Top of Rack (EoR / ToR) applications in data centres.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to 2000 MHz.
Applicable for Power over Ethernet (PoE / PoE+).
- Outer sheath colour orange
- Outer sheath material FRNC/LSZH
- Category Cat.8.2
- Coupling attenuation 75 dB
- Delay Skew 10 ns/100 m
- Shielding shielded
- GBit\s Up to 40 Gbit/s
- Impedance at 100 MHz, ±5Ω 100 Ω
- Loop resistance at 20°C 135 Ω/km
- Near end unbalance attenuation LCL at 1-600 MHz 20 dB
- NVP % 75
- operating capacity 44 pF/m
-
Transfer impedance 1/10/30 MHz
8/10/40 mΩ/m
- Installation temperature 0 °C - +50 °C
- Operating temperature -20 °C - +60 °C
- Field of application Indoor
- Imprint DATWYLER «cable type» «additional text» «batch number» «meter marks»
- Wire colour white/blue-white, white/orange-white, white/green-white, white/brown-white (with length stripes)
- AWG 23
- Minimum bending radius during installation 64 mm
- Minimum bending radius permanently installed 32 mm
- Minimal crush resistance / 10cm 1000 N
- Minimum number of impacts 3
- Solid / Flex Solid wire
- Tensile strength (4P) 110 N
- Reaction to fire (Euroclasses) EN 13501-6: Cca
- Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2
- Flame Propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
- Flame Spread IEC 60332-3-24, EN 60332-3-24
- Smoke Density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2
- Cat./Class Cat.8.2 / Class I/II
- PoE IEEE 802.3bt Type 4 (100W)
Documentation
Versions
Article No. | Stock | Product | AWG | Reaction To Fire | Dimensions n x p x [mm (AWG)] | Number of pairs | Number of Cores | Diameter mm | Outer sheath dimensions [mm] | CU rate [kg/km] | Weight [kg/km] | Fire load [kWh/m] | Number of cables | Packing unit | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
19200900CK
|