CU 6552 4P / 2x4P F8
Data cable, F/FTP, Category 6A, AWG 23, Euroclass B2ca
500 MHz
1 Inner conductor: AWG23 Bare copper wire
2 PE insulated conductor: 1.3 mm Ø
3 Screen (pair): Alu PETP foil
4 Drain wire: Tinned copper wire
5 Overall screen: Alu PETP foil
6 Outer sheath: FRNC/LS0H orange RAL 2003












Description
Electrically and mechanically improved quality Cat.6A data cable – fulfils the requirements of ISO/IEC 11801, IEC 61156-5, EN 50173-1 and prEN 50288-10-1.
Excellent shielding effect due to individually screened pairs and overall foil screen.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
-
Data cable for structured premises cabling.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class EA applications (500 MHz) in accordance with EN 50173-1 and ISO/IEC 11801.
Applicable for Power over Ethernet (PoE) / PoE+.
- Category Cat.6A
- Coupling attenuation 70 dB
- Delay skew 5 ns/100 m
- Shielding shielded
- GBit/s Up to 10 Gbit/s
- Impedance at 100 MHz, ±5Ω 100 Ω
- Loop resistance at 20 °C 150 Ω/km
- Near end unbalance attenuation LCL at 1-600 MHz 40 dB
- NVP % 79
- Operating capacity 42 pF/m
-
Transfer impedance 1/10/30 MHz
50/100/200 mΩ/m
- Installation temperature 0 °C - +50 °C
- Operating temperature -20 °C - +60 °C
- Outer sheath colour orange
- Outer sheath material FRNC/LSZH
- Imprint DATWYLER «cable type» «additional text» «batch number» «meter marks»
- Field of application Indoor
- Wire colour white/blue, white/orange, white/green, white/brown, according to IEC 60189 and IEC 60708
- AWG 23
- Minimum bending radius during installation 56 mm
- Minimum bending radius permanently installed 28 mm
- Minimal crush resistance / 10cm 1000 N
- Minimum number of impacts 10
- Solid / Flex Solid wire
- Tensile strength (2x4P) 190 N
- Tensile strength (4P) 95 N
- Reaction to fire (Euroclasses) EN 13501-6: B2ca
- Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
- Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
- Flame spread IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2
- Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
- Cables standard ISO/IEC 61156-5, EN 50288-10-1
- Cat./Class Cat.6A / Class EA
- PoE IEEE 802.3bt Type 4 (100W)
Documentation
Versions
Article No. | Stock | Product | AWG | Reaction to fire | Dimensions n x p x [mm (AWG)] | Number of pairs | Number of cores | Diameter mm | Outer sheath dimensions [mm] | CU rate [kg/km] | Weight [kg/km] | Fire load [kWh/m] | Number of cables | Packing unit | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
19145400BL
|
CU 6552 4P | AWG23 | B2ca-s1a,d1,a1 | 4 x 2 x 0.55 (AWG23) | 4 | 2 | 0.55 mm | 7 | 20.0 | 49 | 0.14 kWh/m | 1 | 500 m drum | 40393910030860 | |
19145400BK
|
CU 6552 4P | AWG23 | B2ca-s1a,d1,a1 | 4 x 2 x 0.55 (AWG23) | 4 | 2 | 0.55 mm | 7 | 20.0 | 50 | 0.14 kWh/m | 1 | 1000 m drum | 40393910030877 | |
19145600BL
|
CU 6552 2x4P | AWG23 | B2ca-s1,d1,a1 | 2 x (4 x 2 x 0.55 (AWG23)) | 4 | 2 | 0.55 mm | 7.0 x 14.3 | 40.0 | 98 | 0.28 kWh/m | 2 | 500 m drum | 40393910030693 |