Back to: Copper cables

CU 7702 4P / 2x4P F8

Data cable, S/FTP, Category 7A, AWG22, Euroclass B2ca
1300 MHz

1 Inner conductor: AWG22 Bare copper wire
2 PE insulated conductor: 1.5 mm ∅
3 Screen (pair): Alu PETP foil
4 Overall screen: Tinned braided copper
5 Outer sheath: FRNC/LSOH orange RAL 2003

Description

Electrically and mechanically superior quality Cat.7A data cable – exceeds the requirements of ISO/IEC 11801, IEC 61156-5, IEC 61156-7, EN 50173-1 and prEN 50288-9-1.
Excellent shielding effect due to individually screened pairs and overall copper braid.
Easy identification of wires thanks to longitudinal colour markings.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.

  • Data cable for structured premises cabling.
    For the transmission of digital and analogue voice, video and data signals.
    Suitable for all ICT network applications up to class FA applications (1000 MHz) in accordance with EN 50173-1 and ISO/IEC 11801 and for the transmission of broadband signals (such as cable TV) in accordance with IEC 15018.
    Due to the increased wire section eminently suited for Power over Ethernet (PoE) / PoE+ and 4PPoE up to 100W.
  • Outer sheath material FRNC/LSZH
  • Outer sheath colour orange
  • Category Cat.7A
  • Coupling attenuation 85 dB
  • Delay skew 15 ns/100 m
  • Shielding shielded
  • GBit/s Up to 10 Gbit/s
  • Impedance at 100 MHz, ±5Ω 100 Ω
  • Loop resistance at 20 °C 116 Ω/km
  • Near end unbalance attenuation LCL at 1-600 MHz 40 dB
  • NVP % 76
  • Operating capacity 43 pF/m
  • Transfer impedance 1/10/30 MHz 5/5/8 mΩ/m
  • Installation temperature 0 °C - +50 °C
  • Operating temperature -20 °C - +60 °C
  • Imprint DATWYLER «cable type» «additional text» «batch number» «meter marks»
  • Field of application Indoor
  • Wire colour white/blue-white, white/orange-white, white/green-white, white/brown-white (with length stripes)
  • AWG 22
  • Minimum bending radius during installation 64 mm
  • Minimum bending radius permanently installed 32 mm
  • Minimal crush resistance / 10cm 1000 N
  • Minimum number of impacts 10
  • Solid / Flex Solid wire
  • Tensile strength (2x4P) 240 N
  • Tensile strength (4P) 120 N
  • Reaction to fire (Euroclasses) EN 13501-6: B2ca
  • Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
  • Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
  • Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
  • Flame spread IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2
  • Cables standard ISO/IEC 61156-5, EN 50288-9-1
  • Cat./Class Cat.7A / Class FA
  • PoE IEEE 802.3bt Type 4 (100W)

Documentation

EN DE NL FR CN ES IT
Datasheet Datasheet Datasheet Datasheet Datasheet file-icon Datasheet Datasheet
GHMT PVP Certificates GHMT PVP Certificates GHMT PVP Certificates file-icon file-icon file-icon file-icon file-icon
Tender text Tender text Tender text Tender text Tender text file-icon file-icon file-icon
Transmission Parameter file-icon Transmission Parameter file-icon file-icon file-icon file-icon file-icon

Versions

Article No. Stock Product AWGReaction to fireDimensions n x p x [mm (AWG)]Number of pairsNumber of coresDiameter mmOuter sheath dimensions [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]Number of cablesPacking unitGTIN / EAN
17740000BK CU 7702 4P AWG22 B2ca-s1a,d1,a1 4 x 2 x 0.62 (AWG22) 4 2 0.62 7.6 34.9 62 0.18 kWh/m1 1000 m drum 40393910043327