Back to: Copper cables

CU 8206 4P flex

Flexible data cable, S/FTP, Category 8.2, AWG26, Euroclass Dca
2000 MHz

1 Inner conductor: AWG26, bare copper wire, stranded
2 PE insulated conductor: Ø 0.99 mm
3 Screen (pair): Alu PETP foil
4 Overall screen: Tinned braided copper
5 Outer sheath: FRNC/LS0H grey, RAL 7035

Description

Electrically and mechanically superior quality Cat.8.2 patch cord – exceeds the requirements of ISO/IEC 11801, IEC 61156-6, EN 50173-1, EN 50288-4-2 and IEC 61156-10.
Excellent shielding effect due to individually screened pairs and overall copper braid. Compact cable design.
Easy wire identification and termination due to different coloured wires.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.

  • Patch cord in patch panels and as equipment connection cable.
    For the transmission of digital and analogue voice, video and data signals.
    Suitable for all ICT network applications up to 2000 MHz.
    Applicable for Power over Ethernet (PoE / PoE+).
  • Category Cat.8.2
  • Coupling attenuation 85 dB
  • Delay skew 4 ns/100 m
  • Shielding shielded
  • GBit/s Up to 40 Gbit/s
  • Impedance at 100 MHz, ±5Ω 100 Ω
  • Loop resistance at 20 °C 270 Ω/km
  • Near end unbalance attenuation LCL at 1-600 MHz 40 dB
  • NVP % 78
  • operating capacity, 1km @ 800Hz 43 pF/m
  • Transfer impedance 10 mΩ/m
  • Transfer impedance 1/10/30 MHz 10 mΩ/m
  • Installation temperature 0 °C - +50 °C
  • Operating temperature -20 °C - +60 °C
  • Outer sheath colour grey
  • Outer sheath material FRNC/LSZH
  • Imprint DATWYLER «cable type» «additional text» «batch number» «meter marks»
  • Field of application Indoor
  • Wire colour white/blue-white, white/orange-white, white/green-white, white/brown-white (with length stripes)
  • Repeated bending 1000 cycles
  • Minimum bending radius 20 mm
  • AWG 26
  • Minimum number of impacts 10
  • Solid / Flex Stranded wire (flexible)
  • Tensile strength (4P) 56 N
  • Reaction to fire (Euroclasses) EN 13501-6: Dca
  • Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2
  • Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
  • Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2
  • Cables standard ISO/IEC 61156-10, EN 50288-12-2
  • Cat./Class Cat.8.2 / Class I/II
  • PoE IEEE 802.3af

Documentation

EN DE NL FR CN ES IT
Datasheet Datasheet Datasheet Datasheet Datasheet file-icon Datasheet Datasheet

Versions

Article No. Stock Product AWGReaction to fireDimensions n x p x [mm² (AWG)]Number of pairsNumber of coresOuter sheath dimensions [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]Number of cablesPacking unitGTIN / EAN
19206800DK CU 8206 4P Flex AWG26 Dca-s2,d1,a1 4 x 2 x 0.132 (AWG26) 4 2 5.8 18.1 37 0.11 kWh/m1 1000 m drum 40393910028003