CU 7120 4P / 2x4P F8
Data cable, S/FTP, Category 7A, AWG 23, Euroclass Dca
1200 MHz
1 Inner conductor: AWG23 Bare copper wire
2 PE insulated conductor: 1.5 mm Ø
3 Screen (pair): Alu PETP foil
4 Overall screen: Tinned braided copper
5 Outer sheath: FRNC/LSOH










Description
Electrically and mechanically advanced quality Cat.7A data cable – fulfils the requirements of ISO/IEC 11801, IEC 61156-5, EN 50173-1 and EN 50288-9-1.
Excellent shielding effect due to individually screened pairs and overall copper braid.
Reduced outer diameter.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
-
Data cable for structured premises cabling.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class FA applications (1000 MHz) in accordance with EN 50173-1 and ISO/IEC 11801 and for the transmission of broadband signals (such as cable TV) in accordance with ISO/IEC 11801-4.
Applicable for Power over Ethernet PoE / PoE+ / 4PPoE up to 100W.
- Outer sheath colour orange
- Outer sheath material FRNC/LSZH
- Category Cat.7A
- Coupling attenuation 85 dB
- Delay Skew 14 ns/100 m
- Shielding shielded
- GBit\s Up to 10 Gbit/s
- Impedance at 100 MHz, ±5Ω 100 Ω
- Loop resistance at 20°C 134 Ω/km
- Near end unbalance attenuation LCL at 1-600 MHz 40 dB
- NVP % 76
- operating capacity 44 pF/m
-
Transfer impedance 1/10/30 MHz
5/5/8 mΩ/m
- Installation temperature 0 °C - +50 °C
- Operating temperature -20 °C - +60 °C
- Field of application Indoor
- Imprint DATWYLER «cable type» «additional text» «batch number» «meter marks»
- Wire colour white/blue, white/orange, white/green, white/brown, according to IEC 60189 and IEC 60708
- AWG 23
- Minimum bending radius during installation 60 mm
- Minimum bending radius permanently installed 30 mm
- Minimal crush resistance / 10cm 1000 N
- Minimum number of impacts 10
- Solid / Flex Solid wire
- Tensile strength (2x4P) 220 N
- Tensile strength (4P) 110 N
- Reaction to fire (Euroclasses) EN 13501-6: Dca
- Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
- Flame Propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
- Flame Spread IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2
- Smoke Density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
- Cat./Class Cat.7A / Class FA
- PoE IEEE 802.3bt Type 4 (100W)
Documentation
Versions
Article No. | Stock | Product | AWG | Reaction To Fire | Dimensions n x p x [mm (AWG)] | Number of pairs | Number of Cores | Diameter mm | Outer sheath dimensions [mm] | CU rate [kg/km] | Weight [kg/km] | Fire load [kWh/m] | Number of cables | Packing unit | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
19146600DK
|
CU 7120 4P | AWG23 | Dca-s2,d1,a1 | 4 x 2 x 0.59 (AWG23) | 4 | 2 | 0.59 mm | 7.6 | 32.3 | 60 | 0.18 kWh/m | 1 | 1000 m drum | 40393910030532 | |
19146600DL
|
CU 7120 4P | AWG23 | Dca-s2,d1,a1 | 4 x 2 x 0.59 (AWG23) | 4 | 2 | 0.59 mm | 7.6 | 32.3 | 60 | 0.18 kWh/m | 1 | 500 m drum | 40393910030525 | |
19146700DL
|
CU 7120 2x4P | AWG23 | Dca-s2,d1,a1 | 2 x (4 x 2 x 0.59 (AWG23)) | 4 | 2 | 0.59 mm | 7.6 x 16.0 | 64.6 | 120 | 0.36 kWh/m | 2 | 500 m drum | 40393910030464 |